| 2006-12-15 16:12:24 | BUILDING REVIEW 2ND CHECKLIST: |
| | 1- ORIGINAL APPLICATION WAS SUBMITTED BY OWNER/BUILDER. |
| | NOW THERE IS A CONTRACTOR ON BOARD. PROVIDE CHANGE OF |
| | CONTRACTOR FORM ALONG WITH RELATED FEES. SEE ATTACHED |
| | COPY OF CHANGE OF CONTRACTOR FORM AND COMPLETE ALL |
| | REQUIRED INFORMATION. |
| | |
| | 2- FLAT ROOF PRODUCT APPROVAL: |
| | A)SPECIFY PROPOSED FASTENING OPTION FOR SELECTED |
| | APPROVED ASSEMBLY ON PAGE 17 OF NOA 02-0212.07 AS |
| | REQUIRED BY CITY POLICY FOR ROOFING PERMITS. SEE |
| | ATTACHED COPY. |
| | |
| | B) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY |
| | GENERAL LIMITATION #7. SEE LAST PAGE OF NOA 02-0212.07. |
| | CALCULATIONS MUST BE DONE ONLY BY ANY ONE OF THE |
| | PROFESSIONALS LISTED IN LIMITATION #7. |
| | |
| | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 4- ENERGY CALCULATIONS SUBMITTED FORM 600B-04 CAN NOT |
| | BE USED FOR SINGLE ASSEMBLY ROOF/CEILING CONSTRUCTION. |
| | SEE GENERAL DIRECTIONS NOTE #1 ON FRONT PAGE OF ENERGY |
| | CALCULATIONS. PROPOSED ADDITION ISSINGLE ASSEMBLY |
| | CONSTRUCTION.PROVIDE PROPER ENERGY CALCULATIONS |
| | FORM. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL FOR SIMPSON CONNECTORS |
| | SPECIFIED ON PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND SPECIFIC SHEET WHERE CONNECTOR |
| | IS SHOWN WITH FASTENING AND UPLIFT SPECIFICATIONS. GO |
| | TO DCA WEBSITE WWW.FLORIDABUILDING.ORG TO DOWNLOAD ALL |
| | PRODUCT APPROVAL INFORMATION. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- TYPICAL WALL SECTION WAS NOT REVISED AS REQUESTED ON |
| | PREVIOUS CHECKLIST. SEE CURRENT SIMPSON CATALOGUE FOR |
| | CORRECT UPLIFT LOADS AND NUMBER OF FASTENERS. |
| | OTHERWISE, ENGINEER TO PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS IF NUMBERS ARE DIFFERENT THAN THOSE TESTED AND |
| | PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (5610805-6712 |