| Plan Review Notes For Permit 06100199 |
| Permit Number |
06100199 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-19 15:50:23 | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS FORM 600C-2004 | | | (SHORT FORM), PER 2004 FBC 13-101.4.1.1 . | | | | | | 2) PLEASE HAVE NEW ENERGY CALCULATIONS SIGNED BY | | | OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2 . | | | | | | 3) PLEASE SHOW ON PLANS THE A/C SUPPLY AIR DUCT SIZE, | | | GRILL SIZE, AND THE CFM'S., PER 2004 FBC/ WPB AMEND. | | | 106.3.5.4(10) . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|