| 2006-10-20 18:57:02 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | CHECK IF IMPACT FEES WILL NEED TO BE PAID.BRING BACK |
| | STAMPED DRAWINGS AND COPY OF PAID RECEIPT. |
| | |
| | 3- PROVIDE ENERGY CALCULATIONSUSING 2004 FORM. |
| | OWNER'AGENT TO SIGN AND DATE FORM AS WELL. |
| | |
| | 4- PROVIDE FLORIDA OR LOCAL PRODUCT APPROVAL AS |
| | REQUIRED BY DCA RULE 9B-72 FOR: |
| | A) FLAT ROOF.SBCCI REPORT SUBMITTED IS ONLY GOOD |
| | FOR UP TO -45PSF UPLIFT PRESSURES. SEE LIMITATIONS OF |
| | PRODUCT ON LAST PAGE OF THE REPORT. NEED PRODUCT THAT |
| | CAN RESIST AT LEAST -89PSF FOR CORNER AREAS. SEE TABLE |
| | 1609.6B FBC 2004.SUBMIT FLORIDA OR LOCAL PRODUCT |
| | APPROVAL AND CLEARLY IDENTIFY SPECIFIC ASSEMBLY TO BE |
| | INSTALLED. READGENERAL LIMITATIONS OF THE PRODUCT AND |
| | PROVIDE REQUIRED INFORMATION. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. PROVIDE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND SPECIFIC PAGE SHOWING THE CONNECTORS. |
| | |
| | C) SINGLE HUNG WINDOWS.ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE WAS SUBMITTED. NEED TO PROVIDE THE |
| | DRAWINGS ALSO. |
| | NOTE: IF SINGLE HUNG WINDOWS HAVE NOT MISSILE IMPACT |
| | GLAZING,THEN NEED TO PROVIDE COMPLETE INFORMATION FOR |
| | STORM SHUTTERS. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITTING |
| | ALL PRODUCT APPROVALS AS REEQUIRED BY SEC. 106.3.3 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 6- BUILDING PERMIT VALUATION WAS UPDATED TO $35970. |
| | SEC. 108.3 CITY AMENDMENTS TO FBC 2004.. OWES $124.13. |
| | |
| | 7- REVISE TYPICAL WALL SECTION DETAIL.NUMBER OF NAILS |
| | AND UPLIFT LOAD FOR CONNECTOR SIMPSON HETAL 20 NEED TO |
| | BE UPDATED. SEE CURRENT SIMPSON CATALOGUE AND REVISE AS |
| | REQUIRED. |
| | |