| 2007-07-26 11:42:13 | DENIED 4TH TIME |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE WITH THE |
| | ADDITION OF BATH 4 AND CABANA BATH.: |
| | |
| | 1. SHEET A15 THE RESUBMITTED ISOMETRIC SANITARY RISER |
| | DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IN THE |
| | FOLLOWING AREAS. PER FBC-2004 CHAPTER 1, SECTION |
| | 106.1.1 CONSTRUCTION DOCUMENTS (ISOMETRIC) SHALL BE OF |
| | SUFFICIENT CLARITY TO THE LOCATION OF THE PROPOSED |
| | WORK. |
| | |
| | A. ALL OF THE GROUND FLOOR PLUMBING (1/2 BATH, |
| | KITCHEN, AND CABANA BATH). PLEASE REFERENCE THE |
| | CORRECTED ISOMETRIC GROUND FLOOR PLUMBING THAT REFLECTS |
| | THE FLOOR PLAN ON THIS SHEET FOR THE RESUBMITTAL. |
| | |
| | B. 2ND FLOOR MASTER BATH DOES NOT INDICATE THE 1/8 |
| | BEND OFFSETS OR WYE FITTINGS AND THE LAV BY SHOWER |
| | BEING INDICATED IN THE WRONG PLACE. THE TRAP IS BEING |
| | INDICATED AS GOING OUT THE BACK WALL. PLEASE INDICATE |
| | THE WASTE ARM AND CORRECT LOCATION OF TRAP. |
| | |
| | C. 2ND FLOOR LAUNDRY: SINK IN LAUNDRY IS MISLABELED, |
| | IT SHOULD BE INDICATED AS A LAUNDRY TRAY (L.T.). THE |
| | LAUNDRY TRAY WASTE ARM IS BEING INDICATED IN THE WRONG |
| | PLACE. |
| | |
| | D. 2ND FLOOR STUDY: THE SINK IS BEING INDICATED ON THE |
| | WRONG SIDE OF THE 4" HORIZONTAL SANITARY PIPE. |
| | |
| | E. 2ND FLOOR BATH 2: THE LAV WASTE IS BEING INDICATED |
| | IN THE WRONG PLACE. |
| | |
| | F. 2ND FLOOR BATH 3 AND 4: FLOOR PLAN ON SHEET A6 ARE |
| | INDICATING A TUBS, BUT THE SANITARY ISOMETRIC ARE |
| | INDICATING SHOWERS. PLEASE CLARIFY OR CORRECT THIS ON |
| | THE RESUBMITTAL. |
| | |
| | 2. SHEET A15 PLUMBING NOTES: PLEASE DELETE THE |
| | FOLLOWING "PROVIDE MINIMUM PITCH 1/4" AT ALL HORIZONTAL |
| | BRANCHES AND SEWER LINES PER 701.01. PLEASE ADD IN ITS |
| | PLACE THE FOLLOWING "SLOPE OF HORIZONTAL DRAIN PIPE PER |
| | TABLE 704.1" ON THE RESUBMITTAL. |
| | |
| | 3. SHEET A15 SANITARY ISOMETRIC RISER PLEASE INDICATE |
| | THE FOLLOWING. |
| | |
| | A. PER FBC-2004 PLUMBING SECTION, 708.3.4: CLEANOUT AT |
| | THE BASE OF THE 4" SOIL STACK TO THE 2ND FLOOR. |
| | |
| | B. PER FBC-2004 PLUMBING SECTION, 708.3.5: PLEASE |
| | INDICATE A TWO-WAY CLEANOUT AT THE JUNCTION OF THE |
| | BUILDING DRAIN AND BUILDING SEWER. |
| | |
| | 4.SHEET A15 2ND FLOOR PLUMBING PLAN: PLEASE CORRECT |
| | THE BRANCH DRAIN TO THE LAUNDRY TO THREE INCH (3") PER |
| | FBC-2004 PLUMBING SECTION 406.3. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |