| 2007-03-20 19:40:52 | ** UNSAT 3RD REVIEW ** |
| | |
| | 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES ARE |
| | STILL MISSING FROM BEING STATED AND SHOWN ON PLANS. |
| | PLEASE SEE THAT THE FOLLOWING ARE LISTED. |
| | 2004 FBC |
| | 2002 NFPA-70 (NEC). |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THAT THE PLANS DO NOT CONTAIN A |
| | SIGNATURE AND PRINTED NAME OF THE PERSON RESPONSIBLE |
| | FOR PLANS AND DESIGN. |
| | FBC 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE THE MASTER BATHROOM WEST WALL SINK |
| | AREA WHICH REQUIRES A GFI WITHIN 3FT OF THE SINKS EDGE. |
| | THE GFI SHOWN BASED ON THE 3/16 SCALE ON PLANS DOES NOT |
| | MEET THE WITHIN 3FT. |
| | 210.52D. |
| | |
| | 4) NOTE: PLEASE SEE THE GROUNDING ELECTRODE TO THE LEFT |
| | OF THE RISER CONTAINS A #3 FOR THE GEC. THE OTHERS WERE |
| | CHANGED TO THE 1/0. |
| | |
| | 5) NOTE: PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS |
| | FROM THE METER TO THE 200AMP MAIN2OF 2 ARE NOT LARGE |
| | ENOUGH. PLEASE SEE RISER SHOWS 1/0'S AND THE MINIMUM |
| | MUST BE 2/0'S PER 310.15B6 |
| | THIS WAS SHOWN THE SAME ON THE PREVIOUS PLANS, HOWEVER |
| | WAS MISSED. PLEASE SEE THE 2/0'S SHOWN AFTER THE MAIN |
| | ARE OK. |
| | |
| | 6) NOTE: PLEASE SEE THE CONDUIT SIZES BASED ON THE SCH |
| | 80 AND BEING SHOWN AS 1 1/2 INCH IS NOT LARGE ENOUGH |
| | FOR THE 3-2/0'S AND THE #6.MUST BE 2INCH MINIMUM. |
| | THIS WAS SHOWN THIS WAY ON PREVIOUS RISER, HOWEVER WAS |
| | NOT COMMENTED ON BY THIS REVIEWER. |
| | |
| | 7) NOTE: PLEASE SEE SHEET A-17 WAS NOT SEALED BY THE |
| | ENGINEER WHICH IS SIGNED AND DATED ON PLANS AND SHEET |
| | ALSO CONTAINS A TITLE BLOCK FOR SAID SHEETS. PLEASE SEE |
| | FS 471.025, FAC 61G15-23.002 |
| | THIS SHEET WAS VOIDED EVEN THOUGH THIS WAS STAMPED. |
| | |
| | ** PLANS ROUTED BACK TO MECHANICAL AS M SHEETS DO NOT |
| | CONTAIN PRINTED NAME AND SIGNATURE FROM ANY RESPONSIBLE |
| | DESIGNER. |
| | |
| | ** PLEASE ONLY VERIFY THE SPACE ON THE WALL BY THE |
| | GARAGE WHICH INDICATES A 400AMP METER AND TWO 200AMP |
| | DISCONNECTS IN A SPACE NOTE ON PLANS AS 4FT, 2INCHES? |
| | THIS DOES NOT SEEM TO BE ENOUGH SPACE BASED ON THE |
| | PLANS AND DIMENSIONS SHOWN WITH THE A/C EQUIPMENT AS |
| | SHOWN. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-03-20 18:45:17 | ZONING COMPLETED 3/16, RECEIVED FROM INCOMING ON 3/20 |