| Date |
Text |
| 2006-12-10 10:27:27 | ***** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE |
| | STILL IN NEED OF ADDRESSING. PLEASE SEE NOTES ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW WITH A "OK" OR "NO" AT |
| | THE SAME NUMERICAL NOTE. PLEASE SEE SOME MAY BE NOTED |
| | AS "NO/OK", WHICH MEANS PART OF THE NOTE MAY HAVE BEEN |
| | ADDRESSED. |
| | |
| | 1) NOTE: OK. LV SECURITY UNDER SEPARATE PERMIT ALONG |
| | WITH POOL.PLEASE KNOW POOL WILL BE UNDER THE 2005 |
| | NEC. (PLEASE SEE GROUNDING CHANGES). |
| | |
| | 2) NOTE: NO, COULD NOT LOCATE THESE NOTED ON PLANS. |
| | PLEASE KNOW AS THE CODE HAS CHANGED IT IS IMPORTANT THE |
| | RELEVANT CODES ARE SHOWN AS NOT TO FALL UNDER NEW CODE |
| | OF 2005 NEC AND THE REVISIONS TO THE 2004 FBC. (REV |
| | #6). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT THE FOLLOWING MINIMUM CODES ARE |
| | REQUIRED ON PLANS. 2002 NFPA-70, 2002 NFPA-72. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK. |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: NO, PLEASE SEE ? BATH WHICH DOES NOT INDICATE |
| | ANY GFI AS REQUIRED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE NUMEROUS LOCATIONS ARE MISSING THE REQUIRED |
| | GFI RECEPT WITHIN 3' OF LAV/SINKS EDGE IN BATHRMS. |
| | 250.52D, 210.8A1 |
| | |
| | 9) NOTE: NO, PLEASE SEE STUDY AND LAUNDRY ROOMS WITH |
| | RECEPTS WITHIN 6' OF SINKS AND NOTE #8 ABOVE. REDLINED |
| | ONCE AGAIN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MANY LOCATIONS ARE MISSING THE GFI |
| | DESIGNATIONS AS REQUIRED PER 210.8A1,A2, A3, A7< PLEASE |
| | SEE MANY OF THESE HAVE BEEN REDLINED, HOWEVER IT IS IN |
| | NO WAY ALL WHICH ARE MISSING THIS DESIGNATION. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: OK. |
| | |
| | 15) NOTE:NO, PLEASE SEE NO RATINGS SHOWN. THE LETTER |
| | FROM FPL DOES NOT GIVE THE RATINGS TO BE INSTALLED ONLY |
| | WHAT IS AVAILABLE AT THE POLE/TRANSFORMER. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE EQUIPMENT |
| | AND SERIES RATINGS SHALL BE COORDINATED BY THE |
| | DESIGNERS. PLEASE SUBMIT. 110.9, 240.12 |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE: OK/NO, PLEASE SEE THREE CIRCUITS ARE SHOWN |
| | HOWEVER THEY ARE ALL SHOWN FOR BEDROOM #2. |
| | PLEASE ADJUST FOR OTHER CIRCUITS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE LIST ALL THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS ON PANEL SCHEDULE(S) TO BE PROVIDED. |
| | PLEASE SEE 210.12, 408.4, |
| | * IT IS KNOWN THAT A NOTE IS ON PLANS, HOWEVER IT IS |
| | REQUIRED TO SHOW THE SPECIFIC BRANCH CIRCUITS AT THIS |
| | TIME. |
| | FBC 106.1.2 ADM IN SECT |
| | |
| | 18) NOTE: OK. |
| | |
| | 19) NOTE: OK, AS ONLY NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | *** IMPORTANT ** PLEASE SEE POSSIBLE MECHANICAL NOTES |
| | FOR THE LOCATION OF THE ATTIC ACCESS TO THE MECHANICAL |
| | EQUIPMENT. PLEASE KNOW, IT SEEMS THE EQUIPMENT IS |
| | FARTHER THAN SIX FT FROM ACCESS. PLEASE SEE MECH REVIEW |
| | COMMENTS, AS THIS WILL CLEARLY AFFECT THE ELECTRICAL |
| | PLANS. |
| | |
| | 20) NOTE:OK. |
| | |
| | 21) NOTE: NO, PLEASE SEE 424.3B FOR MINIMUM OCP FOR |
| | 10KW UNITS. |
| | REDLINED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 424.3B AS THE MINIMUM OCP FOR THE AHU'S |
| | SHALL BE DONE AT 125% (MIN). PLEASE ADJUST ANY |
| | CONDUCTOR SIZES IF NEEDED. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE: NO, SAME NOTE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 220.3B4. PLEASE SHOW ALL RECESSED LTS BASED |
| | ON MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT BE FIGURED |
| | IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON LEGEND FOR |
| | FIXTURES BEING USED. |
| | |
| | 24) NOTE: NO. THE FIXTURE TYPE AS SHOWN DOES NOT MEET |
| | FBC 13-606.1.ABC.1.2.4 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE FIXTURE TYPE FOR RECESSED LIGHTING |
| | PER CHAPTER 13 OF THE 2004 FBC FOR AIR TIGHT CANS ETC. |
| | |
| | 25) NOTE: OK. |
| | |
| | 26) NOTE: OK. |
| | |
| | 27) NOTE: OK, HOWEVER SAME NOTE ONLY BEING NOTED, AS |
| | THE SERVICE IS STILL BEING SHOWN AS OVER HEAD. PLEASE |
| | KNOW, BASED ON THE FPL TRANSFORMER LOCATION AND THE |
| | FUTURE PROPOSED POOL AS SHOWN ON PLANS, THIS MAY BECOME |
| | AN ISSUE AT A FUTURE TIME |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | ** FOR FUTURE REFERENCE, WHEN APPLYING FOR POOL PERMIT, |
| | PLEASE SEE 680.8 FOR ANY OVER HEAD CONDUCTOR CLEARANCES |
| | AS THE SERVICE ON RISER SHOWS THE SEC'S AS OH. |
| | |
| | 28) NOTE: OK. |
| | |
| | 29) NOTE: OK. |
| | |
| | 30) NOTE:NO/OK, PLEASE SEE PLANS DO NOT CONTAIN THE |
| | REQUIRED SIGNATURE OF PERSON RESPONSIBLE FOR PLANS |
| | DESIGN. |
| | FBC ADMIN SECTION 106.1.2 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FS 481.223 FOR REQUIREMENTS OF WHO IS AND IS |
| | NOT PERMITTED TO OFFER ARCHITECTURAL SERVICES AND |
| | PROVIDING SIGNED AND SEALED DOCUMENTS.PLEASE BE SURE |
| | THE ENGINEER OF RECORD AS SIGNING AND SEALING SAID |
| | DOCUMENT IS AWARE OF THIS AND FS 471.025. IF THERE ARE |
| | ANY QUESTIONS, ON THIS PLEASE CONTACT THE STATE'S LEGAL |
| | COUNSEL TO THE BOARD OF ARCHITECT'S. |
| | ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING |
| | RETAINED BY THIS OFFICE AT THIS TIME. |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO REPEAT COMMENTS. PLEASE KNOW THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |