Plan Review Notes
Plan Review Notes For Permit 06100149
Permit Number 06100149
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-16 12:18:21** UNSAT 2ND REVIEW **
  
  
 *** PLEASE SEE NEW PLANS SUBMITTED WHICH IS NOW BEING
 REVIEWED FOR THE FIRST TIME.
  
  
 1) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, FLORIDA STATUTES 471.023 FOR MISSING
 INFORMATION REQUIRED ON TITLE BLOCKS FOR ELECTRICAL
 SHEETS.
 PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER ALSO KNOWN AT THE ENGINEERING BUS #.
  
 2) NOTE: PLEASE SEE THE RISER SHOWS AN EQUIPMENT
 GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS
 OF DISCONNECT WHICH IS PERMITTED PER 250.6 AND
 250.24B.
  
 3) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42 ETC.
  
 ** THE WIND LOAD CALCULATIONS AND FIXTURE INFORMATION
 SEEMS TO BE OK, HOWEVER WILL HAVE FINAL REVIEW BY THE
 BUILDING REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  