| 2007-01-16 12:18:21 | ** UNSAT 2ND REVIEW ** |
| | |
| | |
| | *** PLEASE SEE NEW PLANS SUBMITTED WHICH IS NOW BEING |
| | REVIEWED FOR THE FIRST TIME. |
| | |
| | |
| | 1) NOTE: PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.002, FLORIDA STATUTES 471.023 FOR MISSING |
| | INFORMATION REQUIRED ON TITLE BLOCKS FOR ELECTRICAL |
| | SHEETS. |
| | PLEASE SEE THE MISSING CERTIFICATE OF AUTHORIZATION |
| | NUMBER ALSO KNOWN AT THE ENGINEERING BUS #. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER SHOWS AN EQUIPMENT |
| | GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS |
| | OF DISCONNECT WHICH IS PERMITTED PER 250.6 AND |
| | 250.24B. |
| | |
| | 3) NOTE: PLEASE SHOW ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 ETC. |
| | |
| | ** THE WIND LOAD CALCULATIONS AND FIXTURE INFORMATION |
| | SEEMS TO BE OK, HOWEVER WILL HAVE FINAL REVIEW BY THE |
| | BUILDING REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |