Plan Review Notes
Plan Review Notes For Permit 06100149
Permit Number 06100149
Review Stop M
Sequence Number 1
Notes
Date Text
2006-11-02 07:32:15DENIED:
 PERMIT APPLICATION INDIATES ADDITIONAL PARKING LOT.
 PLAN SHEET A-4 INDICATES NEW 2 STORY CBS ADDITION.IS
 THIS UNDER A SEPARATE PERMIT?
  
 NO MECHANICAL PLANS SUBMITTED PERTAINING TO MECHANICAL.
 PLAN SHEET A-4 AND A-6 SHOW AN "A/C COURTYARD".WAS
 THIS SUBMITTED FOR REFERENCE ONLY?PLEASE INDICATE IF
 THIS AREA IN "ENCLOSED" WITH A ROOF.PLEASE NOTE PER
 2004 FMC 304.9, EQUIPMENT INSTALLED AT GRADE LEVEL
 SHALL BE SUPPORTED ON A LEVEL MINIMUM 3" CONCRETE SLAB
 OR OTHER APPROVED MATERIAL EXTENDING A MINIMUM OF 2"
 ABOVE THE ADJOINING FINISHED GRADE.PLEASE PROVIDE
 ANCHORING DETAIL.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].