| Plan Review Notes For Permit 06100149 |
| Permit Number |
06100149 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-06 15:47:29 | *****DENIED***** | | | | | | | | | | | | 1.SHOW THE LOCATION OF FIRE HYDRANTS, FIRE DEPARTMENT | | | CONNECTIONS, AND /OR ANY OTHER PERTINENT FIRE | | | PROTECTION DEVICES IN THE PROPOSED WORK SITE AREA. | | | | | | 2.NFPA 1, THE UNIFORM FIRE CODE, 2003 EDITION CHAPTER | | | 18 SHALL BE REFERENCED. | | | | | | 3.WHEN/IF IT IS NECESSARY TO SHUT DOWN OR TO | | | COMPROMISE THE FIRE PROTECTION SYSTEM/DEVICES DUE TO | | | THE SCOPE OF WORK, THE FIRE DEPARTMENT SHALL BE | | | NOTIFIED.THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE | | | ALTERNATE MEASURES OF PROTECTION UNTIL THE SYSTEM IS | | | RETURNED TO SERVICE. | | | | | | 4.A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND WITHIN | | | 50FT OF A SINGLE EXTERIOR DOOR PROVIDING ACCESS TO THE | | | INTERIOR OF THE BUILDING.THE AHJ SHALL BE AUTHORIZED | | | TO REQUIRE ADDITIONAL FIRE PROTECTION IF THE SCOPE OF | | | WORK COMPROMISES THIS ACCESSIBILITY. | | | | | | 5.DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF | | | 150FT IN LENGHT SHALL BE PROVIDED WITH APPROVED | | | PROVISIONS FOR THE TURNING AROUND OF FIRE APPARATUS. | | | | | | 6.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF | | | SUPPORTING AND MAINTAINING 32 TONS FOR FIRE APPARATUS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|