Plan Review Notes
Plan Review Notes For Permit 06100149
Permit Number 06100149
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-12-06 15:47:29*****DENIED*****
  
  
  
 1.SHOW THE LOCATION OF FIRE HYDRANTS, FIRE DEPARTMENT
 CONNECTIONS, AND /OR ANY OTHER PERTINENT FIRE
 PROTECTION DEVICES IN THE PROPOSED WORK SITE AREA.
  
 2.NFPA 1, THE UNIFORM FIRE CODE, 2003 EDITION CHAPTER
 18 SHALL BE REFERENCED.
  
 3.WHEN/IF IT IS NECESSARY TO SHUT DOWN OR TO
 COMPROMISE THE FIRE PROTECTION SYSTEM/DEVICES DUE TO
 THE SCOPE OF WORK, THE FIRE DEPARTMENT SHALL BE
 NOTIFIED.THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 ALTERNATE MEASURES OF PROTECTION UNTIL THE SYSTEM IS
 RETURNED TO SERVICE.
  
 4.A FIRE DEPARTMENT ACCESS ROAD SHALL EXTEND WITHIN
 50FT OF A SINGLE EXTERIOR DOOR PROVIDING ACCESS TO THE
 INTERIOR OF THE BUILDING.THE AHJ SHALL BE AUTHORIZED
 TO REQUIRE ADDITIONAL FIRE PROTECTION IF THE SCOPE OF
 WORK COMPROMISES THIS ACCESSIBILITY.
  
 5.DEAD-END FIRE DEPARTMENT ACCESS ROADS IN EXCESS OF
 150FT IN LENGHT SHALL BE PROVIDED WITH APPROVED
 PROVISIONS FOR THE TURNING AROUND OF FIRE APPARATUS.
  
 6.ALL PAVEMENT ROAD SYSTEMS SHALL BE CAPABLE OF
 SUPPORTING AND MAINTAINING 32 TONS FOR FIRE APPARATUS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
  
  