| 2006-11-14 11:27:32 | BUILDING PLAN REVIEW |
| | PERMIT: 06100149 |
| | ADD: 512 SPENCER DRIVE |
| | CONT: HUNTER CONSTRUCTION |
| | TEL: (561)239-8351 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) GEORGE F. WHITE A.I.A. AND ASSOCIATES, INC. DOES NOT |
| | INDICATE THE FIRMS |
| | CERTIFICATE OF AUTHORIZATION IN THE TITLEBLOCK: 481.219 |
| | F.S.CERTIFICATE OF |
| | AUTHORIZATION.THE TITLE BLOCK FOR ANY |
| | SHEET BEARING THE NAME OF AN ARCHITECT |
| | PRACTICING UNDER A FICTITIOUS NAME, A |
| | CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| | SERVICES, SHALL INCLUDE |
| | THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER.ADD THE NUMBER TO EACH SHEET. |
| | THIS MAY BE ADDED BY HAND. |
| | FL ADMINISTRATIVE CODE 61G1-16.004 TITLE BLOCK |
| | INFORMATION REQUIRED 1-6. |
| | |
| | 3) PLEASE PROVIDE ADDITIONAL INFORMATION ONTHE PERMIT |
| | APPLICATION DESCIPTION OF PROJECT, ARE PHASE I AND |
| | PHASE II |
| | PART OF THIS PERMIT? 106.1.2* ADDITIONAL INFORMATION |
| | REQUIRED. |
| | |
| | 4)A-3 & DETAIL B/ A-6 BOTH INDICATE A NEW COVERED |
| | PORTE COCHERE DROP OFF ZONE: |
| | 3A) DETAIL B DOES INDICATE A NEW PORTE COCHERE BUT THE |
| | |
| | DROP OFF ZONE IS NOT HIGHLIGHTED, SIZE PROVIDED NOR |
| | SLOPE OF GRADE INDICATED. |
| | 11-4.6.6 |
| | 11-4.6.6 PASSENGER LOADING ZONES. |
| | PASSENGER LOADING ZONES SHALL PROVIDE AN ACCESS AISLE |
| | AT LEAST 60 INCHES |
| | (1525 MM) WIDE AND 20 FEET (6096 MM) LONG ADJACENT AND |
| | PARALLEL TO THE |
| | VEHICLE PULL-UP SPACE (SEE FIGURE 11-10 ). IF THERE |
| | ARE CURBS BETWEEN |
| | THE ACCESS AISLE AND THE VEHICLE PULL-UP SPACE, THEN A |
| | CURB RAMP |
| | COMPLYING WITH SECTION 11-4.7 SHALL BE PROVIDED. |
| | VEHICLE STANDING |
| | SPACES AND ACCESS AISLES SHALL BE LEVEL WITH SURFACE |
| | SLOPES NOT |
| | EXCEEDING 1:50 (2 PERCENT) IN ALL DIRECTIONS. |
| | |
| | 5) THE COVERED PORTE COCHERE IS NOT PART OF THIS PERMIT |
| | BUT PLEASE PROVIDE |
| | THE CLEAR HEIGHT UNDER THE CANOPY TO COMPLY WITH: |
| | 11-4.6.5 VERTICAL CLEARANCES. PROVIDE MINIMUM VERTICAL |
| | CLEARENCE OF |
| | 114 INCHES AT ACCESSIBLE PASSENGER LOADING ZONES. |
| | |
| | 6) THE COVERED PORTECOCHERE IS NOT PART OF THIS |
| | PERMIT BUT PLEASE TAKE NOTE |
| | OF DETAIL B/ A-6. THE SIDE WALKIS 5'-3" WIDE AND THE |
| | COLUMNS ARE NOT |
| | DIMENSIONED FOR THE PORTE COCHERE BUT SCALE OUT TO BE |
| | 2'-0" WIDE |
| | LEAVING ONLY 3'-3" OF SIDEWALK 44" IS THE MINIMUM FOR A |
| | MEANS OF AN |
| | ACCISSIBLE ROUTE AND MEANS OF EGRESS . |
| | |
| | 7) SHEET A-4 INDICATES ON THE WEST SIDE OF THE EXISTING |
| | ALUMNI BLDG. |
| | DISABLED PARKING SPACES WITH A NEW ACCESS AISLE, |
| | LEADING TO WHAT |
| | APPEARS TO BETHE ENTRANCE OF THE BUILDING WITH |
| | STAIRS, BUT NO RAMP. |
| | ACCESSIBLE PARKING SPACESSERVING A PARTICULAR |
| | BUILDING SHALL BE |
| | LOCATED ON THE SHORTEST SAFELY ACCESSIBLE ROUTE OF |
| | TRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE ROUTE. |
| | |
| | 8) SHEET A4 AND C-2 AGAIN ON THE WEST SIDE OF THE |
| | ALUMNI BLDG. THERE |
| | APPEARS TO BE A DROP OFF ZONE, NOT LABELED AS SUCH BUT |
| | THE SIDEWALK IS |
| | DROPPED IN THIS AREA, BUTDOESN'T LEAD TO ANY |
| | ACCESSIBLE ROUTE? |
| | |
| | 9)C-10 DETAIL# 10 INDICATES AN ACCESSIBLE CURB CUT, |
| | BUT THIS IS NOT THE DETAIL |
| | INDICATED ON THE WEST SIDE OF THE ALUMNI BLDG. |
| | |
| | 10) SHEET A-6 THE PLANS INDICATE A CHANGE OF GRADE OF |
| | 1/2" |
| | OUT OF A 2 STORY CBS ADDITION, |
| | 11-4.5.2 CHANGES IN LEVEL. |
| | CHANGES IN LEVEL UP TO ? INCHES (6 MM) MAY BE VERTICAL |
| | AND WITHOUT |
| | EDGE TREATMENT [SEE FIGURE 11-7 (C)]. CHANGES IN LEVEL |
| | BETWEEN ? INCH |
| | AND ? INCH (6 MM AND 13 MM) SHALL BE BEVELED WITH A |
| | SLOPE NO GREATER |
| | THAN 1:2 [SEE FIGURE 11-7 (D)]. CHANGES IN LEVEL |
| | GREATER THAN ? INCH (13 MM) |
| | SHALL BE ACCOMPLISHED BY MEANS OF A RAMP THAT COMPLIES |
| | WITH |
| | SECTION 11-4.7 OR 11-4.8 . |
| | |
| | 11) SHEET A-4 THE 3 NEW PARKING SPACES JUST TO THE |
| | SOUTH OF THE NEW |
| | 2 STORY ADDITION ARE MISSING A DISABLED PARKING SPACE. |
| | |
| | 11-4.6.2 LOCATION. |
| | ACCESSIBLE PARKING SPACES SERVING A PARTICULAR BUILDING |
| | SHALL BE |
| | LOCATED ON THE SHORTEST SAFELY ACCESSIBLE ROUTE OF |
| | TRAVEL FROM |
| | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. 11-4.1.2(5) |
| | PARKING SPACES: REQUIRED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |
| | |
| | |
| | |