Date Text
2006-12-08 14:00:11**** UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEW
 WHICH IS STILL IN NEED OF ADDRESSING ALONG WITH SOME
 NEW NOTES WITH THE CHANGES MADE ON PLANS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH A NOTATION OF "NO" OR "OK".
 PLEASE SEE SOME MAY BE NOTED AS "OK/NO" AS PART OF THE
 COMMENT MAY HAVE BEEN ADDRESSED HOWEVER NOT FULLY.
  
 1) NOTE: OK..
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE SEE THE NOTE WAS LOCATED ABOUT H
 NON-BONDING OF THE NEUTRAL, HOWEVER A NOTE OR
 INDICATION FOR THE REQUIRED "FLOATING NEUTRAL" COULD
 NOT LOCATE DON THE RISER. THIS IS BEING REQUESTED AS WE
 HAVE HAD NUMEROUS SITUATIONS OUT IN THE FIELD WHERE
 THIS IS NOT BEING DONE CORRECTLY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE/ NOTE THE "FLOATING NEUTRAL" AT THE
 TENANT METERS. 250.6, 250.24B.
  
 6) NOTE:NO, PLEASE SEE 13-415.1.ABC.1.1, AND .1.2.
 PLEASE SEE CONTROLS REQUIRED COULD NOT BE LOCATED.
 PLEASE SEE PREVIOUS REVIEW NOTE.
 PLEASE SEE ENERGY CALCULATIONS WHICH MENTIONS "MANUAL
 ON/OFF" YET, ACTUALLY THIS SHOULD INDICATE "AUTO"
 ON/OFF"ON THE PROGRAM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR MIN
 LIGHTING CONTROLS FOR EACH SPACE.
 PLEASE SEE 13-415.2.ABC.1 FOR MAX LPD'S. (LIGHTING
 POWER DENSITIES).
  
 7) NOTE: OK/NO, PLEASE SEE POWER PLANS WHICH THE ROOM
 #'S ARE NOT ON PLANS. THIS IS OK ON THE LIGHTING
 PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ROOM/OFFICE DESIGNATIONS SPECIFIC TO
 ROOM OR AREA. IE; OFFICE RECEPTS 101, OFFICE RECEPTS
 104, ETC.
 408.6, 240.4, 310.16.
 FBC 106.1.2
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: NO/OK. PLEASE SEE THE LOCATIONS ARE NOW BEING
 SHOWN; HOWEVER PLEASE SEE NOTE ON RISER MENTIONS 25FT
 MAX FOR THE CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER YET PLEASE SEE 240.21C AS THE CONDUCTORS ON
 THE SECONDARY SIDE ARE ONLY PERMITTED AT 25FT IN A
 DIFFERENT SCENARIO. PLEASE ADJUST NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY AND SHOW LOCATIONS OF TRANSFORMERS.
 PLEASE ALSO PROVIDE MORE OF A DETAIL FOR THE "TAPS"
 BEING DONE ON THE PRIMARY SIDES OF THE TRANSFORMERS FOR
 THE VAV'S.
 PLEASE SEE 240.21, 450.9 ETC
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-12-08 09:18:04REMOVED FROM INCOMING, IN ELECTRICA FOR REVIEW AND WILL
 BE ROUTED BACK TO INCOMING ONCE COMPLETED.