| Plan Review Notes For Permit 06100138 |
| Permit Number |
06100138 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-27 14:39:38 | DENIED; | | | 1. SEE ELECTRICAL PLAN REVIEW'S NOTE 2. | | | 2. ADD TO KEY NOTE #7 NO DEAD ENDS INSANITARY | | | DRAINAGE SYSTEM LONGER THAN 2 FT PLUMBING INSPECTION | | | REQUIRED. | | | 3.BREAK ROOM SINKS SHALL COMPLY WITH FBC-2004 CHAPTER | | | 11 SECTIONS 11-4.24.2 THRU 11-4.24.7. | | | 11-4.24.2HEIGHT OF SINK | | | 11-4.24.3KNEE CKEARANCE | | | 11-4.24.4DEPTH OF SINK | | | 11-4.25.5CLEAR FLOOR SPACE | | | 11-4.25.6EXPOSED PIPES | | | 11-4.24.7FAUCETS | | | SHOW ALL MEASUREMENTS PERTAINING TO ABOVE CODES ON | | | PAGE A-2 ELEVATION 1 | | | SHOW CLEAR FLOOR SPACE ON FLOOR PLAN. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|