Plan Review Notes
Plan Review Notes For Permit 06100138
Permit Number 06100138
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-27 14:39:38DENIED;
 1. SEE ELECTRICAL PLAN REVIEW'S NOTE 2.
 2. ADD TO KEY NOTE #7 NO DEAD ENDS INSANITARY
 DRAINAGE SYSTEM LONGER THAN 2 FT PLUMBING INSPECTION
 REQUIRED.
 3.BREAK ROOM SINKS SHALL COMPLY WITH FBC-2004 CHAPTER
 11 SECTIONS 11-4.24.2 THRU 11-4.24.7.
 11-4.24.2HEIGHT OF SINK
 11-4.24.3KNEE CKEARANCE
 11-4.24.4DEPTH OF SINK
 11-4.25.5CLEAR FLOOR SPACE
 11-4.25.6EXPOSED PIPES
 11-4.24.7FAUCETS
 SHOW ALL MEASUREMENTS PERTAINING TO ABOVE CODES ON
 PAGE A-2 ELEVATION 1
 SHOW CLEAR FLOOR SPACE ON FLOOR PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695