Plan Review Notes
Plan Review Notes For Permit 06100138
Permit Number 06100138
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-13 15:29:10 
  
 ***** UNSAT ******
  
 1) NOTE: PLEASE SEE THE FOLLOWING MINIMUM CODES SHALL
 BE REFELECTED ON PLANS.2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101 FBC 2004. SOME OF THESE ARE SHOWN ON
 ARCHITECTURAL PLANS, HOWEVER SHOULD ALSO BE ON
 ELECTRICAL PLANS.
  
 2) NOTE: PLEASE BE SURE PLANS ARE SIGNED WITH SIGNATURE
 AS ON FILE AND RECOGNIZED BY THE CITY OF WEST PALM
 BEACH.
 FS 471.025
  
 3) NOTE: PLEASE INDICATE THE CONTINUOUS LOADS AT 125%.
 215.3, 230.42
  
 4) NOTE: PLEASE INDICATE MIN AIC RATINGS ON THE OCP
 DEVICES AT MAINS.
 110.9, FBC 106.1.2
  
 5) NOTE: PLEASE INDICATE/ NOTE THE "FLOATING NEUTRAL"
 AT THE TENANT METERS. 250.6, 250.24B.
  
 6) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3
 FOR MIN LIGTHING CONTROLS FOR EACH SPACE.
 PLEASE SEE 13-415.2.ABC.1 FOR MAX LPD'S. (LIGHTING
 POWER DENSITIES).
  
 7) NOTE: PLEASE PROVIDE ROOM/OFFICE DESIGNATIONS
 SPECIFIC TO ROOM OR AREA. IE; OFFICE RECEPTS 101,
 OFFICE RECETPS 104, ETC.
 408.6, 240.4, 310.16.
 FBC 106.1.2
  
 8) NOTE: PLEASE LIST THE MIN LIGHTING/AUDIO LEVELS
 REQUIRED PER2004 FBC ADA 11-4.28. IT IS NOTED ON
 PLANS, HOWEVER SPECIFIC LEVELS IS REQUIRED TO BE SHOWN
 FOR EACH.
  
 9) NOTE: PLEASE VERIFY RISER AS THIS SHOWS "NEUTRAL"
 CONDUCTORS ON THE LINE SIDE OF THE TRANSFORMERS? PLEASE
 SEE 250.20,250.30, ETC.
  
 10) NOTE: PLEASE VERIFY AND SHOW LOCATIONS OF
 TRANSFORMERS. PLEASE ALSO PROVIDEMORE OF A DETAIL FOR
 THE "TAPS" BEING DONE ON THE PRIMARY SIDES OF THE
 TRANSFORMERS FOR THE VAV'S.
 PLEASE SEE 240.21, 450.9 ETC
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved