| 2007-08-09 14:24:35 | REVISION DENIED |
| | REFERENCE: |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET P1 WOMENS RM #105 PLEASE CORRELATE TH FOUR |
| | LAVS INDICATED ON THE ISOMETRIC REVISION WITH THE |
| | UNDERGROUND FLOOR PLAN REVISION PER FBC-2004 CHAPTER 1, |
| | SECTION 106.1.1. |
| | |
| | 2. SHEET P1 SANITARY ISOMETRIC THE FLOOR DRAIN IN MENS |
| | ROOM #104 AND WOMENS ROOM #105 NEED TRAPS PER FBC-2004 |
| | PLUMBING, SECTION 1002.1. |
| | |
| | 3. SHEETS P1 AND P2 THE DATE ON THE SEAL FOR THE |
| | ENGINEER IS NOT LEGIBLE. PER FAC 61G15-23.002(2) THIS |
| | IS REQUIRED TO BE LEGIBLE. |
| | |
| | 4. WHERE IS THE THREE INCH (3") SANITARY FROM THE 2ND |
| | FLOOR LOCATED ON THE REVISION? HAS THIS BEEN DELETED? |
| | PLEASE CLARIFY THIS ON THE RESUBMITTAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |