Plan Review Notes
Plan Review Notes For Permit 06100125
Permit Number 06100125
Review Stop P
Sequence Number 4
Notes
Date Text
2007-08-09 14:24:35REVISION DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET P1 WOMENS RM #105 PLEASE CORRELATE TH FOUR
 LAVS INDICATED ON THE ISOMETRIC REVISION WITH THE
 UNDERGROUND FLOOR PLAN REVISION PER FBC-2004 CHAPTER 1,
 SECTION 106.1.1.
  
 2. SHEET P1 SANITARY ISOMETRIC THE FLOOR DRAIN IN MENS
 ROOM #104 AND WOMENS ROOM #105 NEED TRAPS PER FBC-2004
 PLUMBING, SECTION 1002.1.
  
 3. SHEETS P1 AND P2 THE DATE ON THE SEAL FOR THE
 ENGINEER IS NOT LEGIBLE. PER FAC 61G15-23.002(2) THIS
 IS REQUIRED TO BE LEGIBLE.
  
 4. WHERE IS THE THREE INCH (3") SANITARY FROM THE 2ND
 FLOOR LOCATED ON THE REVISION? HAS THIS BEEN DELETED?
 PLEASE CLARIFY THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]
  