Plan Review Notes
Plan Review Notes For Permit 06100125
Permit Number 06100125
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-17 10:27:59 
 ** UNSAT **
  
 1) NOTE: PLEASE SEE THE PLANS ARE TO BE SUBMITTED AS A
 MINIMUM OF TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 PLEASE DO NOT SUBMIT ALL SETS AS INDIVIDUAL SHEETS.
 PLEASE ALSO BE SURE THE PLANS ARE ATTACHED IN CORRECT
 FASHION SO THAT SETS CAN FALL APART ETC.
 FBC106.1
  
 2) NOTE: PLEASE SEE THE PLANS ARE NOW BEING DESIGNED BY
 A DIFFERENT ENGINEER OF RECORD HOWEVER NO CORRECT
 DOCUMENTATION OF PROCEDURES HAVE BEEN SUBMITTED FOR
 CORRECT TAKING OVER OF PROJECT.
 PLEASE SUBMIT LETTER(S) FROM OWNER RELEASING THE
 ENGINEER OF RECORD AS THE PLANS STATES THIS IS AT THE
 REQUEST OF THE OWNER.
 PLEASE SUBMIT THE CORRECT LETTERS FROM NEW ENGINEER OF
 RECORD ETC. PLEASE KNOW THAT ALL LETTERS MUST BE
 ORIGINAL, NOTARIZED, SIGNED, DATED AND SEALED ETC.
 PLEASE SEE FS 117.05, 471 ETC.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE BELOW:
 PLEASE THE NEW ENGINEER OF RECORD IS RESPONSIBLE. THE
 STATEMENT ON PLANS FOR *AS-BUILTS* DOES NOT COORDINATE
 WITH THE REQUIREMENTS WHICH COME FORM THE FAC AND FS.
 AS THE PLANS SUBMITTED AT THE SAME EXACT SHEETS ETC AS
 ORIGINAL PLANS FROM THE DESIGNER OF RECORD, ONE SET IS
 BEING RETAINED AT THIS TIME. ALL DOCUMENTATION NEEDS TO
 BE SUBMITTED.
 61G15-27.001 PROCEDURES FOR A SUCCESSOR PROFESSIONAL
 ENGINEER ADOPTING AS HIS OWN THE WORK OF ANOTHER
 ENGINEER.
 (1) A SUCCESSOR PROFESSIONAL ENGINEER SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 PROFESSIONAL ENGINEER'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL
 PROFESSIONAL ENGINEER. IN OTHER WORDS, CALCULATIONS,
 SITE VISITS, RESEARCH AND THE LIKE MUST BE DOCUMENTED
 AND PRODUCEABLE UPON DEMAND. FURTHER, THE SUCCESSOR
 PROFESSIONAL ENGINEER MUST TAKE ALL PROFESSIONAL AND
 LEGAL RESPONSIBILITY FOR THE DOCUMENTS WHICH HE SEALED
 AND SIGNED AND CAN IN NO WAY EXEMPT HIMSELF FROM SUCH
 FULL RESPONSIBILITY. PLANS NEED NOT BE REDRAWN BY THE
 SUCCESSOR PROFESSIONAL ENGINEER; HOWEVER, JUSTIFICATION
 FOR SUCH ACTION MUST BE AVAILABLE THROUGH WELL KEPT AND
 COMPLETE DOCUMENTATION ON THE PART OF THE SUCCESSOR
 PROFESSIONAL ENGINEER AS TO HIS HAVING RETHOUGHT AND
 REWORKED THE ENTIRE DESIGN PROCESS. A SUCCESSOR
 PROFESSIONAL ENGINEER MUST USE HIS OWN TITLE BLOCK,
 SEAL AND SIGNATURE AND MUST REMOVE THE TITLE BLOCK,
 SEAL AND SIGNATURE OF THE ORIGINAL PROFESSIONAL
 ENGINEER BEFORE REUSING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING AND SIGNING WORK A SUCCESSOR
 PROFESSIONAL ENGINEER SHALL BE REQUIRED TO NOTIFY THE
 ORIGINAL PROFESSIONAL ENGINEER, HIS SUCCESSORS, OR
 ASSIGNS BY CERTIFIED LETTER TO THE LAST KNOWN ADDRESS
 OF THE ORIGINAL PROFESSIONAL ENGINEER OF THE
 SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 PROFESSIONAL ENGINEER'S WORK. THE SUCCESSOR
 PROFESSIONAL ENGINEER WILL TAKE FULL RESPONSIBILITY FOR
 THE DRAWING AS THOUGH THEY WERE THE SUCCESSOR
 PROFESSIONAL ENGINEER'S ORIGINAL PRODUCT.
  
 3) NOTE: PLEASE SEE THE PREVIOUS PLANS AND NOTES ON THE
 PLANS STATE ALL DEVICES WHICH ARE BEING REPLACE ETC ARE
 TO BE OCCUPANCY SENSOR TYPE DEVICES. PLEASE INDICATE
 THE TYPES OF DEVICES PLEASE SEE THAT AS THESE PLANS ARE
 BEING SUBMITTED AS *AS-BUILTS* ALL OF THIS INFORMATION
 SHOULD BE KNOWN AT THIS TIME.
 FBC 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE BE SURE ALL MAXIMUM TIMES ARE STATED FOR
 DEVICES.
  
 4) NOTE: PLEASE SEE RISER HAS BEEN COMPLETELY REVISED
 WHICH NOW INCLUDES AN ATS WHICH IS SHOWN AS EXISTING?
 THIS IS NOT POSSIBLE AS THERE HAS BEEN NO PERMIT FOR
 THIS SCOPE OF WORK WHICH COULD BE LOCATED IN OUR
 SYSTEM.
 PLEASE ALSO SEE THE RISER SHOWS A GEN-SET WHICH NO
 PERMIT RECORD COULD BE LOCATED.
 BOTH OF THESE WILL BE REQUIRED TO BE UNDER SEPARATE
 PERMIT.
 PLEASE KNOW AS THE BASE BUILDING SERVICE RISER DOES
 NEED REVISING FOR THIS; PLEASE SUBMIT THE MANUFACTURES
 SPECS/CUT SHEETS. REVIEW OF THIS SERVICE ENTRANCE RATED
 DEVICE CAN NOT BE VERIFIED AT THIS TIME.
 PLEASE SEE 230.76, 230.79 ETC.
 110.3, 90.7, 702.6 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE 250.6 AND 250.24 AS NO *EQUIPMENT
 GROUNDING CONDUCTORS* ARE PERMITTED BEFORE THE FIRST
 MEANS OF DISCONNECT.
  
 6) NOTE: PLEASE SEE THE PLANS STILL SHOW AND INDICATE
 THE PREVIOUS RISER DIAGRAM.
 FBC 106.1.2
  
 7) NOTE: PLEASE SEE NO HAND DRAWN CHANGES ARE PERMITTED
 TO PLANS. PLEASE BE SURE TO GIVE CHANGES TO THE
 DESIGNER SO THEY CAN BE INCORPORATED INTO THE REVISED
 RISER ETC.
 FS 471/FAC 61G15-23.002
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]