2007-02-20 18:49:34DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
  
 1.MORE INFORMATION IS REQUIRED. SINCE THE COMPLETE
 EXISTING FLOOR PLAN IS NOT SHOWN, AND NOT KNOWING THE
 EXTENT OF THE WORK BEING DONE, PLEASE COMPLY WITH THE
 FOLLOWING:
 A. OK
 B. SHT A-1 LOCKER ROOM TOILETS STALLS SHALL COMPLY
 WITH FIG. 30E. IF TOILETS ARE NOT IN A STALL, THE CLEAR
 FLOOR SPACE SHALL COMPLY WITH FIG. 28. SECTIONS
 11-4.17.3 & 11-4.16.2. ALSO SHOW THE CLEAR FLOOR SPACE
 FOR ALL FIXTURES.
 ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE DOES NOT
 COMPLY WITH FIG. 28.
 C. OK
 D. OK
  
 2. SHT A-5 DETAIL 3/A-1 SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 ****NOT ADDRESSED
 B. 11-4.24.4 SINK DEPTH
 ****NOT ADDRESSED
 C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQUIRED, A MAXIMUM 19" UNDERNEATH THE SINK. - CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.
 ****NOT ADDRESSED
 D. 11-4.24.7 FAUCETS
 ****NOT ADDRESSED
  
 3. OK
  
 4. SHT P1 SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. DISH WASHERS SHALL CONNECT INDIRECTLY TO
 THE SANT. SYSTEM. SECTION 802.1.6. SUBMIT A DETAIL
 SHOWING COMPLIANCE. - BACK TO BACK LAVS IN THE LOCKER
 ROOM AREA ARE NOT VENTED AS SHOWN. (SEE RED LINE
 EXAMPLE ON ONE SET OF PLANS FOR CORRECTION).
 ****RESPONSE NOTED, BUT AN EXTRA FLOOR CLEANOUT IS
 SHOWN ON THE RISER DIAGRAM THAT IS NOT SHOWN IN ONE OF
 THE LOCKER TOILET ROOMS. (NO ROOM NUMBER GIVEN),
  
 5. OK
 6. OK
  
 7. SHT P1 SUBMIT A WATER RISER DIAGRAM SHOWING ALL NEW
 WORK WITH ALL VALVES, PIPE SIZE, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9 AND INSTALLED NEAR
 THE FIXTURES PER PDI-WH 201 AND MANUF. INSTRUCTIONS.
 106.3.5.1.3.
 ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. THE RISER SHOWS DOUBLE LAVS IN
 TOILET ROOM 104 AS THE LAST FIXTURES BEING PICKED UP
 FROM THE OVERHEAD MAINS, BUT THE FLOOR PLAN SHOWS THE
 WATER CLOSETS IN THE LOCKER ROOM TOILETS AS THE LAST
 FIXTURES PRIOR TO THE WATER MAINS BEING CAPPED OFF.
 THERE ARE MANY AREAS THAT INDICATE PIPING BEING
 EXTENDED FROM OR EXTENDED TO OTHER FIXTRUES. THIS IS
 NOT CLEAR AND CAN BE CLEARED UP BY INDICATING A LETTER
 DESIGNATION AS TO WHERE THE EXTENSION WILL BE FROM AND
 TO. EXAMPLE "A" EXTENDED TO "A" OR "B" EXTENDED TO "B"
 ETC. INDICATE ON PLANS. PLEASE CLARIFY.
  
 *************NEW COMMENT*************
  
 1B. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT. THIS CAN BE SUBMITTED WHEN RESUBMITTING FOR THE
 REMODEL PERMIT, OR CAN BE SUBMITTED WHEN APPLYING FOR
 THE GAS PERMIT.
  
 A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  