| 2007-02-20 18:49:34 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | FROM PREVIOUS REVIEW: |
| | |
| | 1.MORE INFORMATION IS REQUIRED. SINCE THE COMPLETE |
| | EXISTING FLOOR PLAN IS NOT SHOWN, AND NOT KNOWING THE |
| | EXTENT OF THE WORK BEING DONE, PLEASE COMPLY WITH THE |
| | FOLLOWING: |
| | A. OK |
| | B. SHT A-1 LOCKER ROOM TOILETS STALLS SHALL COMPLY |
| | WITH FIG. 30E. IF TOILETS ARE NOT IN A STALL, THE CLEAR |
| | FLOOR SPACE SHALL COMPLY WITH FIG. 28. SECTIONS |
| | 11-4.17.3 & 11-4.16.2. ALSO SHOW THE CLEAR FLOOR SPACE |
| | FOR ALL FIXTURES. |
| | ****RESPONSE NOTED, BUT THE CLEAR FLOOR SPACE DOES NOT |
| | COMPLY WITH FIG. 28. |
| | C. OK |
| | D. OK |
| | |
| | 2. SHT A-5 DETAIL 3/A-1 SHOW THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | ****NOT ADDRESSED |
| | B. 11-4.24.4 SINK DEPTH |
| | ****NOT ADDRESSED |
| | C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH |
| | REQUIRED, A MAXIMUM 19" UNDERNEATH THE SINK. - CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE. |
| | ****NOT ADDRESSED |
| | D. 11-4.24.7 FAUCETS |
| | ****NOT ADDRESSED |
| | |
| | 3. OK |
| | |
| | 4. SHT P1 SANITARY RISER DIAGRAM DOES NOT MEET CODE |
| | REQUIREMENTS. DISH WASHERS SHALL CONNECT INDIRECTLY TO |
| | THE SANT. SYSTEM. SECTION 802.1.6. SUBMIT A DETAIL |
| | SHOWING COMPLIANCE. - BACK TO BACK LAVS IN THE LOCKER |
| | ROOM AREA ARE NOT VENTED AS SHOWN. (SEE RED LINE |
| | EXAMPLE ON ONE SET OF PLANS FOR CORRECTION). |
| | ****RESPONSE NOTED, BUT AN EXTRA FLOOR CLEANOUT IS |
| | SHOWN ON THE RISER DIAGRAM THAT IS NOT SHOWN IN ONE OF |
| | THE LOCKER TOILET ROOMS. (NO ROOM NUMBER GIVEN), |
| | |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT P1 SUBMIT A WATER RISER DIAGRAM SHOWING ALL NEW |
| | WORK WITH ALL VALVES, PIPE SIZE, AND WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9 AND INSTALLED NEAR |
| | THE FIXTURES PER PDI-WH 201 AND MANUF. INSTRUCTIONS. |
| | 106.3.5.1.3. |
| | ****RESPONSE NOTED, BUT THE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. THE RISER SHOWS DOUBLE LAVS IN |
| | TOILET ROOM 104 AS THE LAST FIXTURES BEING PICKED UP |
| | FROM THE OVERHEAD MAINS, BUT THE FLOOR PLAN SHOWS THE |
| | WATER CLOSETS IN THE LOCKER ROOM TOILETS AS THE LAST |
| | FIXTURES PRIOR TO THE WATER MAINS BEING CAPPED OFF. |
| | THERE ARE MANY AREAS THAT INDICATE PIPING BEING |
| | EXTENDED FROM OR EXTENDED TO OTHER FIXTRUES. THIS IS |
| | NOT CLEAR AND CAN BE CLEARED UP BY INDICATING A LETTER |
| | DESIGNATION AS TO WHERE THE EXTENSION WILL BE FROM AND |
| | TO. EXAMPLE "A" EXTENDED TO "A" OR "B" EXTENDED TO "B" |
| | ETC. INDICATE ON PLANS. PLEASE CLARIFY. |
| | |
| | *************NEW COMMENT************* |
| | |
| | 1B. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS |
| | PERMIT. THIS CAN BE SUBMITTED WHEN RESUBMITTING FOR THE |
| | REMODEL PERMIT, OR CAN BE SUBMITTED WHEN APPLYING FOR |
| | THE GAS PERMIT. |
| | |
| | A. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2 |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |