| 2007-02-04 13:10:38 | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE THERE ARE SOME COMMENTS FROM THE PREVIOUS |
| | REVIEW WHICH STILL NEED TO BE CLARIFIED AND THERE ARE |
| | NEW COMMENTS BASED ON MORE INFORMATION AND REVIEW OF |
| | THESE SUBMITTED PLANS NOW FOR SINGLE OCCUPANCY. |
| | |
| | 1) NOTE: PLEASE CLARIFY NOTE ON PLANS WHICH REPEATS A |
| | DISCLAIMER FOR *AS-BUILT* CONDITIONS IN WHICH THE |
| | ENGINEER IS NOT RESPONSIBLE FOR. |
| | PLEASE KNOW THAT ANY SCOPE OF WORK WHICH HAS BEEN DONE |
| | WITHOUT INSPECTIONS WILL BE REQUIRED TO BE OPENED UP |
| | FOR VERIFICATION. IT IS NOT THE DETERMINATION OF THE |
| | OWNER TO DECLINE THIS. PLEASE KNOW THAT ANY CONDITIONS |
| | WHICH MAY HAVE LIFE SAFETY OR FIRE HAZARDS ARE TO BE |
| | INSPECTED.THERE IS NOT EXCEPTION. |
| | PLEASE CLARIFY WHAT IS MEANT BY THIS STATEMENT. |
| | WAS PERVIOUS WORK DONE WITHOUT INSPECTIONS? |
| | WAS DRYWALL/ OR WALL COVERINGS INSTALLED WITHOUT |
| | INSPECTIONS? |
| | FBC 106.1(ALL), 105.1(ALL) AND 109.1 (ALL) FROM THE FBC |
| | ADMIN SECTIONS WHICH ARE IN ORDER OF: REQUIRED PERMITS, |
| | CONSTRUCTION DOCUMENTS AND INSPECTIONS REQUIRED. |
| | |
| | 2) NOTE: PLEASE SEE THAT IS HAS BECOME MORE CLEAR THAT |
| | THIS WAS ONE BUILDING WHICH MAY HAVE CONTAIN MULTIPLE |
| | TENANTSAND IS NOW ONLY GOING TO BE ONE TENANT. |
| | PLEASE KNOW THAT THE REVISED RISER SHALL BE REQUIRED TO |
| | CONTAIN ALL MAINS TO BE LABLED. (ONLY 4 OF 6 IS DONE AT |
| | THIS TIME) PLEASE ALSO SEE THAT THE PLANS WILL BE |
| | ROUTED TO ZONING AND BUILDING SHALL REVIEW FOR ONE |
| | TENANT WHICH WILL REQUIRE ONE SINGLE METER. THIS CAN BE |
| | DONE BY WAY OF A CT ON GUTTER AND THE MULTIPLE METERS |
| | SHOWN AT THIS TIME WILL BE REQUIRED TO BE REMOVED. |
| | THE SPACES CAN BE LEFT FOR POSSIBLE INSTALLATION OF |
| | THESE METERS AT A LATER DATE IF THE BUILDING IS EVER |
| | SEPARATED BACK TO MULTIPLE TENANTS. PLEASE KNOW THAT AT |
| | THIS TIME BASED ON SINGLE THE TENANT, AND SEPARATIONS, |
| | THIS WILL BE REQUIRED. |
| | 230.2, 90.4 |
| | FBC 104.6 |
| | PLEASE ALSO SEE ZONING AND BUILDING REQUIREMENTS FOR |
| | ANY OTHER SECTIONS FOR TENANT SEPARATIONS, OR SINGLE |
| | TENANT. |
| | |
| | 3) NOTE: PLEASE SEE FA SHEETS, PLEASE KNOW THE MINIMUM |
| | LEVELS FOR DEVICES SHALL BE PER FBC 11-4.28.1.2 AND |
| | .3(4). THIS COMMENT WAS NOT MADE ELECTRICAL REVIEW ON |
| | PREVIOUS REVIEW AS IT WAS NOT INCLUDED IN THIS |
| | DEPARTMENTS REVIEW PROCESS, HOWEVER IT IS NOW. |
| | PLEASE ADJUST THE DEVICES, AS MANY ARE LISTED AT 15CD. |
| | FBC ADA EXCEEDS THAT OF NFPA-72. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE KITCHEN AS SHOWN. PLEASE |
| | SEE THAT MECHANICAL PLANS SEEM TO INDICATE HOOD(S) ETC |
| | WHICH IS NOT INCLUDED ON ELECTRICAL PLANS. PLEASE SEE |
| | COMMENTS FROM FIRE, MECHANICAL AND POSSIBLE BUILDING |
| | REVIEW FOR GREASE LADEN VAPORS WHICH MAY BE PRESENT AND |
| | THE REQUIREMENTS FOR THIS. THIS WILL AFFECT THE |
| | ELECTRICAL PLANS AS AT THIS POINT THE ELECTRICAL PLANS |
| | DO NOT INDICATE ANY HOODS, CONTROLS, SHUNTS ETC. |
| | (IT IS THE UNDERSTANDING THAT IS DOES NOT MATTER IF |
| | THESE ARE RESIDENTIAL TYPE OF APPLIANCES OR NOT, THE |
| | HAZARD IS STILL THE SAME). |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 5) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9. PLEASE |
| | INDICATE THE MINIMUM LIGHTING LEVELS FOR EGRESS PATHS |
| | AND EGRESS STAIRS MEETING THE CURRENT CODE. NEW OR |
| | EXISTING WHICH MEETS THESE MINIMUM LEVELS. |
| | PLEASE SEE STAIRS SHALL MEET 10FT CANDLES UNDER NORMAL |
| | AND CAN BE DIMINISHED TO 1FT CANDLE UNDER EMERGENCY |
| | CONDITIONS. ALL OTHER FLAT EGRESS PATHS SHALL MEET THE |
| | MINIMUM OF 1FT CANDLE UNDER BOTH.7.8.1.3, 7.9.2.2 |
| | |
| | 6) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR |
| | THE SERVICE. THIS INFORMATION CAN BE PROVIDED BASED ON |
| | PREVIOUS READINGS. 220.35 |
| | 220.3,220.10,220.11,220.13, ETC CONTINUOUS LOADS PER |
| | 215.3, 230.42 |
| | NOTE ON PLANS MENTIONS NO INCREASE IN LOAD, WHICH IS |
| | OK, HOWEVER WHAT IS THE EXISTING LOADS? |
| | FBC 106.3.5.1.2 |
| | |
| | 7) NOTE: PLEASE SEE LDP-1 WHICH IS SHOWN AS A 400A |
| | RATED PANEL WITH FEED THRU TO THE LDP-2 WHICH IS ALSO |
| | RATED AT 400AMPS, YET THE RISER ONLY SHOWS ONE SET OF |
| | 3/0'S AND THE MAIN AT THE SERVICE SHOWS 400AMP OVER |
| | CURRENT PROTECTION FEEDING BOTH OF THESE. |
| | PLEASE CLARIFY. |
| | 240.4, 310.16 ETC. |
| | |
| | 8) NOTE: PLEASE SHOW THE LOCATION OF THE SERVICE ON THE |
| | BUILDING. |
| | 240.24, 110.26 , 408.7 ETC. |
| | PLEASE KNOW THAT ANY INTERIORS PANELS ARE NOT PERMITTED |
| | IN STORAGE CLOSETS ETC. |
| | |
| | 9) NOTE: PLEASE PROVIDE ROOM AND ARE DESIGNATIONS ON |
| | PLANS. |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE PROVIDE PERFOMANCE INFORMATION FOR |
| | LIGHTING LEVELS. 13-415.2. NOTE ON PLANS MENTIONS THAT |
| | NO ENERGY CALCULATIONS ARE REQUIRED, HOWEVER LIGHTING |
| | DENSITES ARE TO BE PROVIDED. |
| | |
| | 11) NOTE: PLEASE SEE THE SEAL FOR THE ENGINEER SHALL BE |
| | RAISED SO THAT ALL INFORMATION ON SAID SEAL IS CLEAR |
| | AND VISIBLE. PLEASE SEE SOME SHEETS ARE VERY FAINT. |
| | FAC 61G15-23.001. |
| | FS 471.025. |
| | |
| | 12) NOTE: THIS COMMENT IS FOR CONTRACTOR; PLEASE SEE |
| | POSSIBLE COMMENTS FROM BUILDING REVIEW WITH RESPECT TO |
| | APPLIED VALUATION FOR SCOPE OF WORK. THE COMPLETE SCOPE |
| | OF WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF |
| | ANY EQUIPMENT IS OWNER SUPPLIED. PLEASE SEE FBC 108.3 |
| | |
| | ** ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |