Plan Review Notes
Plan Review Notes For Permit 06100125
Permit Number 06100125
Review Stop E
Sequence Number 2
Notes
Date Text
2007-02-04 13:10:38*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE SOME COMMENTS FROM THE PREVIOUS
 REVIEW WHICH STILL NEED TO BE CLARIFIED AND THERE ARE
 NEW COMMENTS BASED ON MORE INFORMATION AND REVIEW OF
 THESE SUBMITTED PLANS NOW FOR SINGLE OCCUPANCY.
  
 1) NOTE: PLEASE CLARIFY NOTE ON PLANS WHICH REPEATS A
 DISCLAIMER FOR *AS-BUILT* CONDITIONS IN WHICH THE
 ENGINEER IS NOT RESPONSIBLE FOR.
 PLEASE KNOW THAT ANY SCOPE OF WORK WHICH HAS BEEN DONE
 WITHOUT INSPECTIONS WILL BE REQUIRED TO BE OPENED UP
 FOR VERIFICATION. IT IS NOT THE DETERMINATION OF THE
 OWNER TO DECLINE THIS. PLEASE KNOW THAT ANY CONDITIONS
 WHICH MAY HAVE LIFE SAFETY OR FIRE HAZARDS ARE TO BE
 INSPECTED.THERE IS NOT EXCEPTION.
 PLEASE CLARIFY WHAT IS MEANT BY THIS STATEMENT.
 WAS PERVIOUS WORK DONE WITHOUT INSPECTIONS?
 WAS DRYWALL/ OR WALL COVERINGS INSTALLED WITHOUT
 INSPECTIONS?
 FBC 106.1(ALL), 105.1(ALL) AND 109.1 (ALL) FROM THE FBC
 ADMIN SECTIONS WHICH ARE IN ORDER OF: REQUIRED PERMITS,
 CONSTRUCTION DOCUMENTS AND INSPECTIONS REQUIRED.
  
 2) NOTE: PLEASE SEE THAT IS HAS BECOME MORE CLEAR THAT
 THIS WAS ONE BUILDING WHICH MAY HAVE CONTAIN MULTIPLE
 TENANTSAND IS NOW ONLY GOING TO BE ONE TENANT.
 PLEASE KNOW THAT THE REVISED RISER SHALL BE REQUIRED TO
 CONTAIN ALL MAINS TO BE LABLED. (ONLY 4 OF 6 IS DONE AT
 THIS TIME) PLEASE ALSO SEE THAT THE PLANS WILL BE
 ROUTED TO ZONING AND BUILDING SHALL REVIEW FOR ONE
 TENANT WHICH WILL REQUIRE ONE SINGLE METER. THIS CAN BE
 DONE BY WAY OF A CT ON GUTTER AND THE MULTIPLE METERS
 SHOWN AT THIS TIME WILL BE REQUIRED TO BE REMOVED.
 THE SPACES CAN BE LEFT FOR POSSIBLE INSTALLATION OF
 THESE METERS AT A LATER DATE IF THE BUILDING IS EVER
 SEPARATED BACK TO MULTIPLE TENANTS. PLEASE KNOW THAT AT
 THIS TIME BASED ON SINGLE THE TENANT, AND SEPARATIONS,
 THIS WILL BE REQUIRED.
 230.2, 90.4
 FBC 104.6
 PLEASE ALSO SEE ZONING AND BUILDING REQUIREMENTS FOR
 ANY OTHER SECTIONS FOR TENANT SEPARATIONS, OR SINGLE
 TENANT.
  
 3) NOTE: PLEASE SEE FA SHEETS, PLEASE KNOW THE MINIMUM
 LEVELS FOR DEVICES SHALL BE PER FBC 11-4.28.1.2 AND
 .3(4). THIS COMMENT WAS NOT MADE ELECTRICAL REVIEW ON
 PREVIOUS REVIEW AS IT WAS NOT INCLUDED IN THIS
 DEPARTMENTS REVIEW PROCESS, HOWEVER IT IS NOW.
 PLEASE ADJUST THE DEVICES, AS MANY ARE LISTED AT 15CD.
 FBC ADA EXCEEDS THAT OF NFPA-72.
  
 4) NOTE: PLEASE CLARIFY THE KITCHEN AS SHOWN. PLEASE
 SEE THAT MECHANICAL PLANS SEEM TO INDICATE HOOD(S) ETC
 WHICH IS NOT INCLUDED ON ELECTRICAL PLANS. PLEASE SEE
 COMMENTS FROM FIRE, MECHANICAL AND POSSIBLE BUILDING
 REVIEW FOR GREASE LADEN VAPORS WHICH MAY BE PRESENT AND
 THE REQUIREMENTS FOR THIS. THIS WILL AFFECT THE
 ELECTRICAL PLANS AS AT THIS POINT THE ELECTRICAL PLANS
 DO NOT INDICATE ANY HOODS, CONTROLS, SHUNTS ETC.
 (IT IS THE UNDERSTANDING THAT IS DOES NOT MATTER IF
 THESE ARE RESIDENTIAL TYPE OF APPLIANCES OR NOT, THE
 HAZARD IS STILL THE SAME).
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE SEE NFPA-101 7.8 AND 7.9. PLEASE
 INDICATE THE MINIMUM LIGHTING LEVELS FOR EGRESS PATHS
 AND EGRESS STAIRS MEETING THE CURRENT CODE. NEW OR
 EXISTING WHICH MEETS THESE MINIMUM LEVELS.
 PLEASE SEE STAIRS SHALL MEET 10FT CANDLES UNDER NORMAL
 AND CAN BE DIMINISHED TO 1FT CANDLE UNDER EMERGENCY
 CONDITIONS. ALL OTHER FLAT EGRESS PATHS SHALL MEET THE
 MINIMUM OF 1FT CANDLE UNDER BOTH.7.8.1.3, 7.9.2.2
  
 6) NOTE: PLEASE SUBMIT COMPLETE LOAD CALCULATIONS FOR
 THE SERVICE. THIS INFORMATION CAN BE PROVIDED BASED ON
 PREVIOUS READINGS. 220.35
 220.3,220.10,220.11,220.13, ETC CONTINUOUS LOADS PER
 215.3, 230.42
 NOTE ON PLANS MENTIONS NO INCREASE IN LOAD, WHICH IS
 OK, HOWEVER WHAT IS THE EXISTING LOADS?
 FBC 106.3.5.1.2
  
 7) NOTE: PLEASE SEE LDP-1 WHICH IS SHOWN AS A 400A
 RATED PANEL WITH FEED THRU TO THE LDP-2 WHICH IS ALSO
 RATED AT 400AMPS, YET THE RISER ONLY SHOWS ONE SET OF
 3/0'S AND THE MAIN AT THE SERVICE SHOWS 400AMP OVER
 CURRENT PROTECTION FEEDING BOTH OF THESE.
 PLEASE CLARIFY.
 240.4, 310.16 ETC.
  
 8) NOTE: PLEASE SHOW THE LOCATION OF THE SERVICE ON THE
 BUILDING.
 240.24, 110.26 , 408.7 ETC.
 PLEASE KNOW THAT ANY INTERIORS PANELS ARE NOT PERMITTED
 IN STORAGE CLOSETS ETC.
  
 9) NOTE: PLEASE PROVIDE ROOM AND ARE DESIGNATIONS ON
 PLANS.
 FBC 106.1.2
  
 10) NOTE: PLEASE PROVIDE PERFOMANCE INFORMATION FOR
 LIGHTING LEVELS. 13-415.2. NOTE ON PLANS MENTIONS THAT
 NO ENERGY CALCULATIONS ARE REQUIRED, HOWEVER LIGHTING
 DENSITES ARE TO BE PROVIDED.
  
 11) NOTE: PLEASE SEE THE SEAL FOR THE ENGINEER SHALL BE
 RAISED SO THAT ALL INFORMATION ON SAID SEAL IS CLEAR
 AND VISIBLE. PLEASE SEE SOME SHEETS ARE VERY FAINT.
 FAC 61G15-23.001.
 FS 471.025.
  
 12) NOTE: THIS COMMENT IS FOR CONTRACTOR; PLEASE SEE
 POSSIBLE COMMENTS FROM BUILDING REVIEW WITH RESPECT TO
 APPLIED VALUATION FOR SCOPE OF WORK. THE COMPLETE SCOPE
 OF WORK SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF
 ANY EQUIPMENT IS OWNER SUPPLIED. PLEASE SEE FBC 108.3
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW