2006-11-25 15:01:21DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1.MORE INFORMATION IS REQUIRED. SINCE THE COMPLETE
 EXISTING FLOOR PLAN IS NOT SHOWN, AND NOT KNOWING THE
 EXTENT OF THE WORK BEING DONE, PLEASE COMPLY WITH THE
 FOLLOWING:
 A. SHT A-1 MEN'S TOILET ROOM 104 AND WOMEN'S TOILET
 ROOM 105 ACCESSIBLE STALLS SHALL MEET THE REQUIREMENTS
 OF FIG. 30E CHAPTER 11. 85" WIDTH REQUIRED, 68" WIDTH
 PROVIDED.
 B. SHT A-1 LOCKER ROOM TOILETS STALLS SHALL COMPLY
 WITH FIG. 30E. IF TOILETS ARE NOT IN A STALL, THE CLEAR
 FLOOR SPACE SHALL COMPLY WITH FIG. 28. SECTIONS
 11-4.17.3 & 11-4.16.2. ALSO SHOW THE CLEAR FLOOR SPACE
 FOR ALL FIXTURES.
 C. SHT A-1 SHOW STALL SIZES & CLEAR FLOOR SPACE SHALL
 COMPLY WITH FIG. 11-35(A) OR (B).
 D. SHT A-1 A DRINKING FOUNTAIN IS REQUIRED PER TABLES
 1004.1.2 & 403.1. INDICATE THE LOCATION OF THE DRINKING
 FOUNTAIN. IF THE DRINKING FOUNTAIN IS NOT A HI/LOW,
 SHOW COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS
 FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.
  
 2. SHT A-5 DETAIL 3/A-1 SHOW THE FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH
 REQUIRED, A MAXIMUM 19" UNDERNEATH THE SINK. - CABINET
 DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.D.
 11-4.24.7 FAUCETS
  
 3. SHT A-7 FINISH SCHEDULE. TOILET ROOMS 104, 105, 209,
 210 MEN'S & WOMEN'S RESTROOMS. PAINTED WALLS DO NOT
 COMPLY WITH SECTION 1210.2. REQUIREMENTS FOR SMOOTH,
 "HARD", NONABSORBENT SURFACE. PAINTED WALLS ARE NOT
 CONSIDERED A "HARD" SURFACE.
  
 4. SHT P1 SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. DISH WASHERS SHALL CONNECT INDIRECTLY TO
 THE SANT. SYSTEM. SECTION 802.1.6. SUBMIT A DETAIL
 SHOWING COMPLIANCE. - BACK TO BACK LAVS IN THE LOCKER
 ROOM AREA ARE NOT VENTED AS SHOWN. (SEE RED LINE
 EXAMPLE ON ONE SET OF PLANS FOR CORRECTION).
  
 5. SHT P1 PLUMBING FLOOR PLAN. SHOW THE LOCATION AND
 BUILDING DRAIN LINE FOR THE RISER TO THE SECOND FLOOR
 TO REFLECT THE RISER DIAGRAM. SECTION 106.1.1.
  
 6. SHT P1 2ND FLOOR SANT. RISER DIAGRAM. THE URINAL AS
 SHOWN IS AN "S" TRAP AND IS PROHIBITED PER SECTION
 1002.3. (SEE RED LINE CORRECTION EXAMPLE ON ONE SET OF
 PLANS).
  
 7. SHT P1 SUBMIT A WATER RISER DIAGRAM SHOWING ALL NEW
 WORK WITH ALL VALVES, PIPE SIZE, AND WATER HAMMER
 ARRESTORS REQUIRED BY SECTION 604.9 AND INSTALLED NEAR
 THE FIXTURES PER PDI-WH 201 AND MANUF. INSTRUCTIONS.
 106.3.5.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  