| 2006-11-25 15:01:21 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1.MORE INFORMATION IS REQUIRED. SINCE THE COMPLETE |
| | EXISTING FLOOR PLAN IS NOT SHOWN, AND NOT KNOWING THE |
| | EXTENT OF THE WORK BEING DONE, PLEASE COMPLY WITH THE |
| | FOLLOWING: |
| | A. SHT A-1 MEN'S TOILET ROOM 104 AND WOMEN'S TOILET |
| | ROOM 105 ACCESSIBLE STALLS SHALL MEET THE REQUIREMENTS |
| | OF FIG. 30E CHAPTER 11. 85" WIDTH REQUIRED, 68" WIDTH |
| | PROVIDED. |
| | B. SHT A-1 LOCKER ROOM TOILETS STALLS SHALL COMPLY |
| | WITH FIG. 30E. IF TOILETS ARE NOT IN A STALL, THE CLEAR |
| | FLOOR SPACE SHALL COMPLY WITH FIG. 28. SECTIONS |
| | 11-4.17.3 & 11-4.16.2. ALSO SHOW THE CLEAR FLOOR SPACE |
| | FOR ALL FIXTURES. |
| | C. SHT A-1 SHOW STALL SIZES & CLEAR FLOOR SPACE SHALL |
| | COMPLY WITH FIG. 11-35(A) OR (B). |
| | D. SHT A-1 A DRINKING FOUNTAIN IS REQUIRED PER TABLES |
| | 1004.1.2 & 403.1. INDICATE THE LOCATION OF THE DRINKING |
| | FOUNTAIN. IF THE DRINKING FOUNTAIN IS NOT A HI/LOW, |
| | SHOW COMPLIANCE WITH SECTION 11-4.1.3(10)(A) PROVISIONS |
| | FOR THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 2. SHT A-5 DETAIL 3/A-1 SHOW THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE. (FORWARD APPROACH |
| | REQUIRED, A MAXIMUM 19" UNDERNEATH THE SINK. - CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE.D. |
| | 11-4.24.7 FAUCETS |
| | |
| | 3. SHT A-7 FINISH SCHEDULE. TOILET ROOMS 104, 105, 209, |
| | 210 MEN'S & WOMEN'S RESTROOMS. PAINTED WALLS DO NOT |
| | COMPLY WITH SECTION 1210.2. REQUIREMENTS FOR SMOOTH, |
| | "HARD", NONABSORBENT SURFACE. PAINTED WALLS ARE NOT |
| | CONSIDERED A "HARD" SURFACE. |
| | |
| | 4. SHT P1 SANITARY RISER DIAGRAM DOES NOT MEET CODE |
| | REQUIREMENTS. DISH WASHERS SHALL CONNECT INDIRECTLY TO |
| | THE SANT. SYSTEM. SECTION 802.1.6. SUBMIT A DETAIL |
| | SHOWING COMPLIANCE. - BACK TO BACK LAVS IN THE LOCKER |
| | ROOM AREA ARE NOT VENTED AS SHOWN. (SEE RED LINE |
| | EXAMPLE ON ONE SET OF PLANS FOR CORRECTION). |
| | |
| | 5. SHT P1 PLUMBING FLOOR PLAN. SHOW THE LOCATION AND |
| | BUILDING DRAIN LINE FOR THE RISER TO THE SECOND FLOOR |
| | TO REFLECT THE RISER DIAGRAM. SECTION 106.1.1. |
| | |
| | 6. SHT P1 2ND FLOOR SANT. RISER DIAGRAM. THE URINAL AS |
| | SHOWN IS AN "S" TRAP AND IS PROHIBITED PER SECTION |
| | 1002.3. (SEE RED LINE CORRECTION EXAMPLE ON ONE SET OF |
| | PLANS). |
| | |
| | 7. SHT P1 SUBMIT A WATER RISER DIAGRAM SHOWING ALL NEW |
| | WORK WITH ALL VALVES, PIPE SIZE, AND WATER HAMMER |
| | ARRESTORS REQUIRED BY SECTION 604.9 AND INSTALLED NEAR |
| | THE FIXTURES PER PDI-WH 201 AND MANUF. INSTRUCTIONS. |
| | 106.3.5.1.3. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |