| Plan Review Notes For Permit 06100125 |
| Permit Number |
06100125 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-27 11:00:26 | *** DENIED *** | | | 1) PROVIDE RETURN AIR FOR OFFICE #220, PER 2004 FBC/M | | | 601.4. | | | | | | 2) PLEASE SUBMIT DETAILED MANUFACTURE'S SPECIFICATION'S | | | AND INSTALLATION | | | INSTRUCTIONS FOR GAS COOK TOP AND MICRO/HOOD ABOVE, TO | | | BE INSTALLED IN KITCHEN #103. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|