| 2006-12-14 19:08:58 | *****DENIED***** |
| | |
| | |
| | |
| | 1.THE COMPLETE AND CORRECT ADDRESS IS REQUIRED IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.THIS SHOULD |
| | BE 1801 SOUTH AUSTALIAN AVENUE, WEST PALM BEACH, |
| | FLORIDA. |
| | |
| | 2.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | HINDER OR INTERFERE WITH EMERGENCY ACCESS TO THE |
| | PROPERTY OR VICINITY THEREOF. |
| | |
| | 5.COMBUSTIBLE WASTE, DUST, AND DEBRIS SHALL BE |
| | REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR MORE |
| | FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 6.FIRE EXTINGUISHERS ARE TO BE 2A:10BC RATED AND AT |
| | DISTANCES TO SATISFY THE 75' TRAVEL DISTANCE. |
| | |
| | 7.PROVIDELAYOUT OF THE EXISTING FIRE SPRINKLER |
| | SYSTEM,AND IF EQUIPPED, THE FIRE ALARM SYSTEM.IF |
| | THESE SYSTEMS ARE MODIFIED DUE TO THE SCOPE OF WORK, |
| | SEPARATE PLANS AND PERMIT WILL BE REQUIRED. |
| | |
| | 8.INDICATE INTERIOR FINISH FOR WALLS AND CEILINGS. |
| | CLASS "A" OR CLASS "B" IS REQUIRED IN EXITS AND EXIT |
| | ACCESS CORRIDORS. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |