Plan Review Notes
Plan Review Notes For Permit 06100125
Permit Number 06100125
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-26 09:24:55**** UNSAT ******
  
 1) NOTE: PLEASE BE SURE TO PLACE ALL RELEVANT CODES ON
 PLANS: 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 AND
 OTHER CODES WHICH MAY BE REQUIRED FOR OTHER TRADES .
 NFPA--96 ETC.
  
 2) NOTE: PLEASE EXPLAIN WHAT SEEMS TO BE A FULL KITCHEN
 BEING INSTALLED WITH A GAS STOVE. PLEASE INCLUDE ALL
 INFORMATION FOR HOOD/SHUNTS FOR ANY ELECTRICAL ETC.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL AFFECT
 ALL PLANS AND ALL TRADES.
  
 3) NOTE: PLEASE SEE 210.8B3 FOR GFI PROTECTION REQUIRED
 IN KITCHEN IN OTHER THAN DWELLING UNITS FOR ALL15/20A
 120VRECEPTS WHETHER OR NOT THEY FEED COUNTER SPACES.
  
 4) NOTE: PLEASE ALSO SEE 210.8B FOR OTHER AREAS FOR GFI
 PROTECTION REQUIRED WHICH IS NOT CLARIFIED AT THIS
 TIME. (BATH RMS ETC).
  
 5) NOTE; PLEASE STATE TYPE OF OCCUPANT SENSORS WHICH
 ARE NOTED FOR INSTALLATION. PLEASE SEE A NOTE PLACED ON
 PLANS IN LIEU OF DETAIL AND SPECIFICS IS NOT
 PERMITTED.
 PLEASE SEE 13-415.1.ABC.1.2. (TIMER TYPE 4HRS MAX, OS
 TYPE 30MINS MAX) SHOW SYMBOL AND CORRELATE WITH SYMBOL
 LEGEND.
  
 6) NOTE: PLEASE SEE SERVICE. THIS IS UNCLEAR AT THIS
 TIME AS THE BUILDING SEEMS TO BE ALL ONE OCCUPANT AT
 THIS TIME.?? PLEASE SEE THE SEC'S ARE BEING SHOWN AS A
 SINGLE PHASE SERVICE, YET NOTE AT RISER, PANELS ETC
 INDICATE A 3PHASE SERVICE?
 PLEASE CORRELATE.
  
 7) NOTE: PLEASE ALSO SEE THERE ARE MAINS BEING LOCATED
 ON THE "LINE" SIDE OF THE THE FPL METERS ON RISER???
 PLEASE SEE FPL MIN SERVICE STANDARDS AS THIS SEEMS TO
 BE REVERSED OR ARE THE METERS ACTUALLY NOT FPL
 DEVICES.
  
 8) NOTE: PLEASE LABEL ALL MAINS. PLEASE ALSO COMPLETE
 AND LABEL ALL PANELS OR MAINS WHICH FEEDS PANELS. IT IS
 UNCLEAR AT THIS TIME WHERE ALL PANELS ARE FED FROM,
 AMPERAGE, ETC
 230.70, 230.72, 240.4, 215.5, 310.16 ETC MANY ITEMS CAN
 NOT BE VERIFIED AT THIS TIME.
  
 9) NOTE: PLEASE SEE RISER SHOWS "EQUIPMENT GROUNDING
 CONDUCTORS" INSTALLED FROM THE SERVICE ENTRANCE GUTTER
 TO THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED. PLEASE SEE 250.6, 250.24B
  
 10) NOTE: PLEASE COMPLETE PANEL SCHEDULES TO CORRELATE
 ALL CIRCUITING TO ROOMS AND AREAS IN WHICH THEY FEED.
 SCHEDULE SHOULD BE SPECIFIC. IE; OFFICE 102 RECEPTS,
 KITCHEN LT'S, RECEPTION RECPTS ETC.
 PLEASE PLACE ALL ROOM AND ARE DESIGNATIONS ON PLANS. IF
 A NUMERICAL IDENTIFICATION IS DESIRED THIS IS OK.
 240.4,310.16,408.4.
 FBC 106.1.2 ADMIN SECT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2006-10-25 12:57:02IN ELECTRICAL FOR REVIEW