| Date |
Text |
| 2006-10-26 09:24:55 | **** UNSAT ****** |
| | |
| | 1) NOTE: PLEASE BE SURE TO PLACE ALL RELEVANT CODES ON |
| | PLANS: 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 AND |
| | OTHER CODES WHICH MAY BE REQUIRED FOR OTHER TRADES . |
| | NFPA--96 ETC. |
| | |
| | 2) NOTE: PLEASE EXPLAIN WHAT SEEMS TO BE A FULL KITCHEN |
| | BEING INSTALLED WITH A GAS STOVE. PLEASE INCLUDE ALL |
| | INFORMATION FOR HOOD/SHUNTS FOR ANY ELECTRICAL ETC. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL AFFECT |
| | ALL PLANS AND ALL TRADES. |
| | |
| | 3) NOTE: PLEASE SEE 210.8B3 FOR GFI PROTECTION REQUIRED |
| | IN KITCHEN IN OTHER THAN DWELLING UNITS FOR ALL15/20A |
| | 120VRECEPTS WHETHER OR NOT THEY FEED COUNTER SPACES. |
| | |
| | 4) NOTE: PLEASE ALSO SEE 210.8B FOR OTHER AREAS FOR GFI |
| | PROTECTION REQUIRED WHICH IS NOT CLARIFIED AT THIS |
| | TIME. (BATH RMS ETC). |
| | |
| | 5) NOTE; PLEASE STATE TYPE OF OCCUPANT SENSORS WHICH |
| | ARE NOTED FOR INSTALLATION. PLEASE SEE A NOTE PLACED ON |
| | PLANS IN LIEU OF DETAIL AND SPECIFICS IS NOT |
| | PERMITTED. |
| | PLEASE SEE 13-415.1.ABC.1.2. (TIMER TYPE 4HRS MAX, OS |
| | TYPE 30MINS MAX) SHOW SYMBOL AND CORRELATE WITH SYMBOL |
| | LEGEND. |
| | |
| | 6) NOTE: PLEASE SEE SERVICE. THIS IS UNCLEAR AT THIS |
| | TIME AS THE BUILDING SEEMS TO BE ALL ONE OCCUPANT AT |
| | THIS TIME.?? PLEASE SEE THE SEC'S ARE BEING SHOWN AS A |
| | SINGLE PHASE SERVICE, YET NOTE AT RISER, PANELS ETC |
| | INDICATE A 3PHASE SERVICE? |
| | PLEASE CORRELATE. |
| | |
| | 7) NOTE: PLEASE ALSO SEE THERE ARE MAINS BEING LOCATED |
| | ON THE "LINE" SIDE OF THE THE FPL METERS ON RISER??? |
| | PLEASE SEE FPL MIN SERVICE STANDARDS AS THIS SEEMS TO |
| | BE REVERSED OR ARE THE METERS ACTUALLY NOT FPL |
| | DEVICES. |
| | |
| | 8) NOTE: PLEASE LABEL ALL MAINS. PLEASE ALSO COMPLETE |
| | AND LABEL ALL PANELS OR MAINS WHICH FEEDS PANELS. IT IS |
| | UNCLEAR AT THIS TIME WHERE ALL PANELS ARE FED FROM, |
| | AMPERAGE, ETC |
| | 230.70, 230.72, 240.4, 215.5, 310.16 ETC MANY ITEMS CAN |
| | NOT BE VERIFIED AT THIS TIME. |
| | |
| | 9) NOTE: PLEASE SEE RISER SHOWS "EQUIPMENT GROUNDING |
| | CONDUCTORS" INSTALLED FROM THE SERVICE ENTRANCE GUTTER |
| | TO THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| | PERMITTED. PLEASE SEE 250.6, 250.24B |
| | |
| | 10) NOTE: PLEASE COMPLETE PANEL SCHEDULES TO CORRELATE |
| | ALL CIRCUITING TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | SCHEDULE SHOULD BE SPECIFIC. IE; OFFICE 102 RECEPTS, |
| | KITCHEN LT'S, RECEPTION RECPTS ETC. |
| | PLEASE PLACE ALL ROOM AND ARE DESIGNATIONS ON PLANS. IF |
| | A NUMERICAL IDENTIFICATION IS DESIRED THIS IS OK. |
| | 240.4,310.16,408.4. |
| | FBC 106.1.2 ADMIN SECT. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-10-25 12:57:02 | IN ELECTRICAL FOR REVIEW |