| 2006-11-14 13:59:02 | BUILDING PLAN REVIEW |
| | PERMIT: 06100125 |
| | ADD: 1801 S. AUSTRALIAN AVE. |
| | CONT: E. B. MORRIS G. C. |
| | TEL: (904)237-9252 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2)FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) 106.1.2* ADDITIONAL INFORMATION REQUIRED. |
| | 3A)SHEET A-1, PLEASE PROVIDE INFORMATION IF THIS IS A |
| | SINGLE TENANT ON THE FIRST FLOOR? OR IF THIS IS A |
| | SINGLE |
| | TENANT FOR THE WHOLE BUILDING? |
| | |
| | 3B) SHEET A-1 ROOMS AND DOORS ARE NOT IDENTIFIED, |
| | PLEASE PROVIDE IDENTIFICATION OF ROOMS AND DOORS. IF |
| | THERE ARE MULTIPLE TENANTS PLEASE INDICATE THE |
| | OCCUPANT |
| | LOADS OF ROOMS. |
| | |
| | 3C) SHEET A-1 LOCKER ROOM SHOWERS PROVIDE DETAILS FOR |
| | THE SHOWERS TO BE ACCESSIBLE, THIS AREA IS BEING |
| | RECONFIGURED NEEDING TO COMPLY WITH . |
| | 11-4.23.3 CLEAR FLOOR SPACE. |
| | THE ACCESSIBLE FIXTURES AND CONTROLS REQUIRED IN |
| | SECTIONS 11-4.23.4 , 11-4.23.5 , 11-4.23.6 , 11-4.23.7 |
| | , 11-4.23.8 AND 11-4.23.9 SHALL BE ON AN ACCESSIBLE |
| | ROUTE. AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH |
| | SECTION 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE |
| | BATHROOM. THE CLEAR FLOOR SPACES AT FIXTURES AND |
| | CONTROLS, THE ACCESSIBLE ROUTE, AND THE TURNING SPACE |
| | MAY OVERLAP. |
| | 11-4.23.7 CONTROLS AND DISPENSERS. |
| | IF CONTROLS, DISPENSERS, RECEPTACLES, OR OTHER |
| | EQUIPMENT ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL |
| | BE ON AN ACCESSIBLE ROUTE AND SHALL COMPLY WITH SECTION |
| | 11-4.27 . |
| | 11-4.21 SHOWER STALLS. |
| | |
| | 11-4.21.1 GENERAL. |
| | ACCESSIBLE SHOWER STALLS SHALL COMPLY WITH SECTION |
| | 11-4.21 . |
| | |
| | 11-4.21.2 SIZE AND CLEARANCES. |
| | EXCEPT AS SPECIFIED IN SECTION 11-9.1.2 , SHOWER STALL |
| | SIZE AND CLEAR FLOOR SPACE SHALL COMPLY WITH FIGURE |
| | 11-35 (A) OR FIGURE 11-35 (B). THE SHOWER STALL IN |
| | FIGURE 11-35 (A) SHALL BE 36 INCHES BY 36 INCHES (915 |
| | MM BY 915 MM). SHOWER STALLS REQUIRED BY SECTION |
| | 11-9.1.2 SHALL COMPLY WITH FIGURE 11-57 (A) OR FIGURE |
| | 11-57 (B). THE SHOWER STALL IN FIGURE 11-35 (B) WILL |
| | FIT INTO THE SPACE REQUIRED FOR A BATHTUB. |
| | |
| | 11-4.21.3 SEAT. |
| | A SEAT SHALL BE PROVIDED IN SHOWER STALLS 36 INCHES BY |
| | 36 INCHES (915 MM BY 915 MM) AND SHALL BE AS SHOWN IN |
| | FIGURE 11-36 . THE SEAT SHALL BE MOUNTED 17 INCHES TO |
| | 19 INCHES (430 MM TO 485 MM) FROM THE BATHROOM FLOOR |
| | AND SHALL EXTEND THE FULL DEPTH OF THE STALL. IN A |
| | 36-INCH BY 36-INCH (915 MM BY 915 MM) SHOWER STALL, THE |
| | SEAT SHALL BE ON THE WALL OPPOSITE THE CONTROLS. WHERE |
| | A FIXED SEAT IS PROVIDED IN A 30-INCH BY 60-INCH |
| | MINIMUM (760 MM BY 1525 MM) SHOWER STALL, IT SHALL BE A |
| | FOLDING TYPE AND SHALL BE MOUNTED ON THE WALL ADJACENT |
| | TO THE CONTROLS AS SHOWN IN FIGURE 11-57 . THE |
| | STRUCTURAL STRENGTH OF SEATS AND THEIR ATTACHMENTS |
| | SHALL COMPLY WITH SECTION 11-4.26.3 . |
| | |
| | 11-4.21.4 GRAB BARS. |
| | GRAB BARS COMPLYING WITH SECTION 11-4.26 SHALL BE |
| | PROVIDED AS SHOWN IN FIGURE 11-37 . |
| | |
| | 11-4.21.5 CONTROLS. |
| | FAUCETS AND OTHER CONTROLS COMPLYING WITH SECTION |
| | 11-4.27.4 SHALL BE LOCATED AS SHOWN IN FIGURE 11-37 . |
| | IN SHOWER STALLS 36 INCHES BY 36 INCHES (915 MM BY 915 |
| | MM), ALL CONTROLS, FAUCETS, AND THE SHOWER UNIT SHALL |
| | BE MOUNTED ON THE SIDE WALL OPPOSITE THE SEAT. |
| | |
| | 11-4.21.6 SHOWER UNIT. |
| | A SHOWER SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES |
| | (1525 MM) LONG THAT CAN BE USED BOTH AS A FIXED SHOWER |
| | HEAD AND AS A HAND-HELD SHOWER SHALL BE PROVIDED. |
| | EXCEPTION: IN UNMONITORED FACILITIES WHERE VANDALISM IS |
| | A CONSIDERATION, A FIXED SHOWER HEAD MOUNTED AT 48 |
| | INCHES (1220 MM) ABOVE THE SHOWER FLOOR MAY BE USED IN |
| | LIEU OF A HAND-HELD SHOWER HEAD. |
| | |
| | 11-4.21.7 CURBS. |
| | IF PROVIDED, CURBS IN SHOWER STALLS 36 INCHES BY 36 |
| | INCHES (915 MM BY 915 MM) SHALL BE NO HIGHER THAN ? |
| | INCH (13 MM). SHOWER STALLS THAT ARE 30 INCHES BY 60 |
| | INCHES (760 MM BY 1525 MM) MINIMUM SHALL NOT HAVE |
| | CURBS. |
| | |
| | 11-4.21.8 SHOWER ENCLOSURES. |
| | IF PROVIDED, ENCLOSURES FOR SHOWER STALLS SHALL NOT |
| | OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER FROM WHEELCHAIRS |
| | ONTO SHOWER SEATS. |
| | |
| | 3D) RESTROOM CLOSETS HAVE 1'-6" DOORS NEED TO COMPLY |
| | WITH : |
| | 11-4.13.5 CLEAR WIDTH. |
| | DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32 |
| | INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED |
| | BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP [SEE |
| | FIGURE 11-24 (A), FIGURE 11-24 (B), FIGURE 11-24 (C), |
| | AND FIGURE 11-24 (D)]. OPENINGS MORE THAN 24 INCHES |
| | (610 MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1 |
| | AND 11-4.3.3 [SEE FIGURE 11-24 (E)]. |
| | |
| | 3E) DOORS 6-11 FIRST FLOOR MINIMUM WIDTH, |
| | |
| | 3F) FIRST FLOOR KITCHEN SINK CABINET NEEDS TO PROVIDE |
| | FOR FRONT APPROACH. |
| | 11-4.24.5 CLEAR FLOOR SPACE. |
| | A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| | (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4 |
| | SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD |
| | APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN |
| | ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19 |
| | INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 11-32 |
| | ). |
| | |
| | 3G)SHEET A-1 DOOR NOTES INDICATE 2001 FAC WITH |
| | CURRENT AMENDMENTS, PLEASE CORRECT. |
| | |
| | 4)A-2 WINDOWS 202 & 221 ARE INDICATED AS NEW |
| | OPENINGS: |
| | FL BLD CODE 1609.1.4: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A)IMPACT WINDOWS |
| | |
| | 5)PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 6 ) WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7)A-2 THE WOMENS RESTROOM ON THE 2ND FLOOR INDICATES |
| | WORK |
| | BEING COMPLETED UNDER THIS PERMIT, THIS RESTROOM NEEDS |
| | |
| | TO HAVE AN ACCESSIBLE STALL IN CONFORMANCE WITH FIGURE |
| | 30, TOLIET STALLS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |