Plan Review Notes
Plan Review Notes For Permit 06100125
Permit Number 06100125
Review Stop B
Sequence Number 1
Notes
Date Text
2006-11-14 13:59:02BUILDING PLAN REVIEW
 PERMIT: 06100125
 ADD: 1801 S. AUSTRALIAN AVE.
 CONT: E. B. MORRIS G. C.
 TEL: (904)237-9252
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) 106.1.2* ADDITIONAL INFORMATION REQUIRED.
 3A)SHEET A-1, PLEASE PROVIDE INFORMATION IF THIS IS A
 SINGLE TENANT ON THE FIRST FLOOR? OR IF THIS IS A
 SINGLE
 TENANT FOR THE WHOLE BUILDING?
  
 3B) SHEET A-1 ROOMS AND DOORS ARE NOT IDENTIFIED,
 PLEASE PROVIDE IDENTIFICATION OF ROOMS AND DOORS. IF
 THERE ARE MULTIPLE TENANTS PLEASE INDICATE THE
 OCCUPANT
 LOADS OF ROOMS.
  
 3C) SHEET A-1 LOCKER ROOM SHOWERS PROVIDE DETAILS FOR
 THE SHOWERS TO BE ACCESSIBLE, THIS AREA IS BEING
 RECONFIGURED NEEDING TO COMPLY WITH .
 11-4.23.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS REQUIRED IN
 SECTIONS 11-4.23.4 , 11-4.23.5 , 11-4.23.6 , 11-4.23.7
 , 11-4.23.8 AND 11-4.23.9 SHALL BE ON AN ACCESSIBLE
 ROUTE. AN UNOBSTRUCTED TURNING SPACE COMPLYING WITH
 SECTION 11-4.2.3 SHALL BE PROVIDED WITHIN AN ACCESSIBLE
 BATHROOM. THE CLEAR FLOOR SPACES AT FIXTURES AND
 CONTROLS, THE ACCESSIBLE ROUTE, AND THE TURNING SPACE
 MAY OVERLAP.
 11-4.23.7 CONTROLS AND DISPENSERS.
 IF CONTROLS, DISPENSERS, RECEPTACLES, OR OTHER
 EQUIPMENT ARE PROVIDED, THEN AT LEAST ONE OF EACH SHALL
 BE ON AN ACCESSIBLE ROUTE AND SHALL COMPLY WITH SECTION
 11-4.27 .
 11-4.21 SHOWER STALLS.
  
 11-4.21.1 GENERAL.
 ACCESSIBLE SHOWER STALLS SHALL COMPLY WITH SECTION
 11-4.21 .
  
 11-4.21.2 SIZE AND CLEARANCES.
 EXCEPT AS SPECIFIED IN SECTION 11-9.1.2 , SHOWER STALL
 SIZE AND CLEAR FLOOR SPACE SHALL COMPLY WITH FIGURE
 11-35 (A) OR FIGURE 11-35 (B). THE SHOWER STALL IN
 FIGURE 11-35 (A) SHALL BE 36 INCHES BY 36 INCHES (915
 MM BY 915 MM). SHOWER STALLS REQUIRED BY SECTION
 11-9.1.2 SHALL COMPLY WITH FIGURE 11-57 (A) OR FIGURE
 11-57 (B). THE SHOWER STALL IN FIGURE 11-35 (B) WILL
 FIT INTO THE SPACE REQUIRED FOR A BATHTUB.
  
 11-4.21.3 SEAT.
 A SEAT SHALL BE PROVIDED IN SHOWER STALLS 36 INCHES BY
 36 INCHES (915 MM BY 915 MM) AND SHALL BE AS SHOWN IN
 FIGURE 11-36 . THE SEAT SHALL BE MOUNTED 17 INCHES TO
 19 INCHES (430 MM TO 485 MM) FROM THE BATHROOM FLOOR
 AND SHALL EXTEND THE FULL DEPTH OF THE STALL. IN A
 36-INCH BY 36-INCH (915 MM BY 915 MM) SHOWER STALL, THE
 SEAT SHALL BE ON THE WALL OPPOSITE THE CONTROLS. WHERE
 A FIXED SEAT IS PROVIDED IN A 30-INCH BY 60-INCH
 MINIMUM (760 MM BY 1525 MM) SHOWER STALL, IT SHALL BE A
 FOLDING TYPE AND SHALL BE MOUNTED ON THE WALL ADJACENT
 TO THE CONTROLS AS SHOWN IN FIGURE 11-57 . THE
 STRUCTURAL STRENGTH OF SEATS AND THEIR ATTACHMENTS
 SHALL COMPLY WITH SECTION 11-4.26.3 .
  
 11-4.21.4 GRAB BARS.
 GRAB BARS COMPLYING WITH SECTION 11-4.26 SHALL BE
 PROVIDED AS SHOWN IN FIGURE 11-37 .
  
 11-4.21.5 CONTROLS.
 FAUCETS AND OTHER CONTROLS COMPLYING WITH SECTION
 11-4.27.4 SHALL BE LOCATED AS SHOWN IN FIGURE 11-37 .
 IN SHOWER STALLS 36 INCHES BY 36 INCHES (915 MM BY 915
 MM), ALL CONTROLS, FAUCETS, AND THE SHOWER UNIT SHALL
 BE MOUNTED ON THE SIDE WALL OPPOSITE THE SEAT.
  
 11-4.21.6 SHOWER UNIT.
 A SHOWER SPRAY UNIT WITH A HOSE AT LEAST 60 INCHES
 (1525 MM) LONG THAT CAN BE USED BOTH AS A FIXED SHOWER
 HEAD AND AS A HAND-HELD SHOWER SHALL BE PROVIDED.
 EXCEPTION: IN UNMONITORED FACILITIES WHERE VANDALISM IS
 A CONSIDERATION, A FIXED SHOWER HEAD MOUNTED AT 48
 INCHES (1220 MM) ABOVE THE SHOWER FLOOR MAY BE USED IN
 LIEU OF A HAND-HELD SHOWER HEAD.
  
 11-4.21.7 CURBS.
 IF PROVIDED, CURBS IN SHOWER STALLS 36 INCHES BY 36
 INCHES (915 MM BY 915 MM) SHALL BE NO HIGHER THAN ?
 INCH (13 MM). SHOWER STALLS THAT ARE 30 INCHES BY 60
 INCHES (760 MM BY 1525 MM) MINIMUM SHALL NOT HAVE
 CURBS.
  
 11-4.21.8 SHOWER ENCLOSURES.
 IF PROVIDED, ENCLOSURES FOR SHOWER STALLS SHALL NOT
 OBSTRUCT CONTROLS OR OBSTRUCT TRANSFER FROM WHEELCHAIRS
 ONTO SHOWER SEATS.
  
 3D) RESTROOM CLOSETS HAVE 1'-6" DOORS NEED TO COMPLY
 WITH :
 11-4.13.5 CLEAR WIDTH.
 DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32
 INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP [SEE
 FIGURE 11-24 (A), FIGURE 11-24 (B), FIGURE 11-24 (C),
 AND FIGURE 11-24 (D)]. OPENINGS MORE THAN 24 INCHES
 (610 MM) IN DEPTH SHALL COMPLY WITH SECTIONS 11-4.2.1
 AND 11-4.3.3 [SEE FIGURE 11-24 (E)].
  
 3E) DOORS 6-11 FIRST FLOOR MINIMUM WIDTH,
  
 3F) FIRST FLOOR KITCHEN SINK CABINET NEEDS TO PROVIDE
 FOR FRONT APPROACH.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 11-32
 ).
  
 3G)SHEET A-1 DOOR NOTES INDICATE 2001 FAC WITH
 CURRENT AMENDMENTS, PLEASE CORRECT.
  
 4)A-2 WINDOWS 202 & 221 ARE INDICATED AS NEW
 OPENINGS:
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A)IMPACT WINDOWS
  
 5)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6 ) WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 7)A-2 THE WOMENS RESTROOM ON THE 2ND FLOOR INDICATES
 WORK
 BEING COMPLETED UNDER THIS PERMIT, THIS RESTROOM NEEDS
  
 TO HAVE AN ACCESSIBLE STALL IN CONFORMANCE WITH FIGURE
 30, TOLIET STALLS.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  