| Plan Review Notes For Permit 06100099 |
| Permit Number |
06100099 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-19 17:58:21 | | | | | | | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS AND | | | RECOMMENDATION, REGARDING CLEARANCES FOR THE | | | GENERATOR. | | | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE | | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | | RESUBMITTING. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|