| 2006-12-05 18:41:12 | **** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE |
| | STILL IN QUESTION. PLEASE ALSO SEE ANY NEW NOTES DUE TO |
| | PLANS SUBMITTED. |
| | ** PLEASE SEE A NOTE OF "NO" OR "OK" IS BEING NOTED AT |
| | EACH NOTE WHICH IS TAKEN DIRECTLY FROM PREVIOUS REVIEW. |
| | PLEASE SEE IF NO, A FURTHER EXPLANATION IS NOTED TO |
| | BETTER CLEAR UP COMMENT FROM PREVIOUS REVIEW. PLEASE |
| | KNOW SOME MAY SHOW NO/OK, THIS MAY BE THAT PART OF THE |
| | COMMENT WAS ADDRESSED AND PART OF THE COMMENT MAY STILL |
| | BE OUTSTANDING. |
| | |
| | |
| | 1) NOTE:NO, PLEASE SEE BASED ON THE LIGHTING |
| | DENSITIES SHOWN, PLEASE SEE TABLES IN 13-415.2.ABC.1, |
| | 415.2.B.1. |
| | PLEASE BE SURE ALL SEPARATE SPACES INDICATE A CONTROL |
| | DEVICE. |
| | PLEASE SEE THAT ALL MAXIMUM TIMES ON DEVICES SHOWN BE |
| | NOTED ON THE LEGEND. |
| | PLEASE SEE IF THE EXISTING CORRIDOR IS GOING TO BE PART |
| | OF THE TENANT SPACE, SEE THAT CONTROLS WILL BE |
| | REQUIRED. |
| | PLEASE SEE THAT A DETAIL OR NOTE IS PROVIDED TO |
| | INDICATE THE CIRCUITING OF ALL EM/EXT LTS SHALL BE |
| | WIRED TO ANY LOCAL BRANCH CIRCUIT AHEAD OF ANY CONTROL |
| | SWITCHING DEVICES. PLEASE SEE 700.12E. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1, .1.2 AND |
| | .1.3. |
| | PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE |
| | WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER |
| | THE 2004 FBC. PLEASE ADJUST AS NEEDED. |
| | |
| | 2) NOTE: NO, THIS IS NOT CLEAR YET AS TENANT SPACES |
| | WITH RATE WALL ETC ARE STILL BE SHOWN, PLEASE SEE NOTE |
| | #3. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE ALL AREAS WHICH ARE BEING SHOWN AS "COMMON |
| | AREAS" MAY NOT BE FED FROM PANELS WHICH ARE FOR TENANT |
| | SPACE.210.25 |
| | |
| | 3) NOTE:NO, PLEASE SEE RESPONSE MENTIONS THIS IS ALL |
| | GOING TO BE ONE TENANT SPACE, HOWEVER PLANS CLEARLY |
| | STILL INDICATE TWO TENANTS. PLEASE SEE NOTE #1 WHICH |
| | SPEAKS OF CIRCUITING OF FIXTURES FOR EXISTING CORRIDOR |
| | AND CIRCUITING TO RECESSED LIGHTS ETC? |
| | PLEASE SEE TENANT SEPARATION WALLS AND MULTIPLE TENANTS |
| | ARE STILL BEING SHOWN. IF THIS "IS" ONE TENANT, PLEASE |
| | ADJUST PLANS ACCORDINGLY. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE ELECTRICAL PANELS MAY NOT BE IN RATED EXIT |
| | CORRIDOR SEE FBC BUILDING REVIEW COMMENTS. IF INDEED |
| | THIS IS GOING TO BE TWO TENANT SPACES PLEASE VERIFY AS |
| | ONLY ONE METER IS BEING SHOWN AND MAY NOT FEED TWO |
| | TENANTS/SEPARATE OCCUPANCIES FROM ONE METER/MAIN. |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWS WHICH MAY AFFECT |
| | THE AMOUNT OF TENANTS ALLOWED PER FLOOR, CORRIDORS |
| | ETC. |
| | PLEASE SEE PREVIOUS NOTE WITH RESPECT TO THE COMMON |
| | AREA NOT BEING FED OR CONTAINING THE ELECTRICAL FROM |
| | TENANT PANEL. |
| | |
| | 4) NOTE: NO, MAY NOT USE A "PLUG-IN" FOR THE REQUIRED |
| | DISCONNECTING MEANS. THIS WAS CHANGED IN THE CODE |
| | BEFORE THE 93 CODE. PLEASE SEE BASED ON THE LOAD AS |
| | SHOWN A HARDWIRED DISCONNECT IS REQUIRED. PLEASE KNOW |
| | IF THE EXISTING INST-HOT IS A PLUG TYPE, THE LOAD MUST |
| | BE LESS THAN 750VA. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS AN |
| | INSTA-HOT., YET COULD NOT FIND THIS ON PLANS. PLEASE |
| | SEE 430.30, 430.31 ETC AS LOAD OF THIS SIZE WHEN UNIT |
| | IS REQUIRED TO CONTAIN A DISCONNECT. A PLUG MAY NOT BE |
| | USED. PLEASE ALSO VERIFY IF THE DISCONNECTING MEANS |
| | CONTAINS OCP, IF SO, PLEASE SEE 110.26. |
| | |
| | 4) NOTE: OK, HOWEVER PLEASE SEE NOTE ABOVE AS IF THE |
| | SPACE IS ONE, THEN CIRCUITING WILL BE REVISED AND WILL |
| | RESULT IN SOME CHANGES TO CIRCUITS ON PLANS AS WELL AS |
| | POSSIBLE PANEL SCHEDULE REVISIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE SPECIFIC ROOMS AND AREAS ON PANEL |
| | SCHEDULE WHICH WILL CORRELATE WITH THE PLANS AND |
| | LAYOUT. 408.6, PLEASE ALSO BE SURE TO INDICATE ALL |
| | CONDUCTOR SIZES ON PANEL SCHEDULE. |
| | 310.16, 240.4 |
| | FBC 106.1.2. |
| | |
| | 5) NOTE: NO/OK, PLEASE SEE THE APPLIED VALUE ON THE |
| | APPLICATION ALONG WITH THE CORRECT SQ FOOT FOR BUILD |
| | OUT MUST BE ADJUSTED BY THE CONTRACTOR TO CORRELATE |
| | WITH PLANS. PLEASE SEE A VALUE HAS BEEN ADJUST TO $50K, |
| | HOWEVER THIS VALUE MAY STILL BE ADJUSTED BY THE |
| | BUILDING REVIEWER BASED ON THE TABLES AS SET FORTH IN |
| | THE FBC. THIS VALUE AMY NOT BE FINAL. |
| | FEES WERE NOTE PAID FOR ADDITIONAL VALUE AND ALL FEES |
| | ARE DUE AT THE TIME OF SUBMITIAL UP TO A VALUE OF |
| | $200K.ONLY THEN CAN A VALUE OF OVER 200K BE ALLLOWED |
| | TO PAY A % UPFRONT. PLEASE KNOW PLANS WILL NOT BE |
| | REVIEWED IF ALL FEES ARE NOT PAID BEFORE RESUBMITTING |
| | PLANS. THIS IS STATE IN 108.3 OF THE ADMINISTRATIVE |
| | CODE AS ADOPTED INTO CITY ORDINANCEANDADMIN CODE. |
| | |
| | **PREVIOUS REVIEW NOTE** |
| | PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK SHALL BE |
| | BASED ON ALL LABOR AND MATERIALS EVEN IF OWNER |
| | SUPPLIED. |
| | FBC 108.3 |
| | PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES |
| | BASED ON THE FBC ONE WILL BE ASSESSED. FEES WILL BE |
| | OWED. |
| | PLEASE KNOW, ONCE THE SQ FT HAS BEEN VERIFIED FOR |
| | ACTUAL SCOPE OF WORK, THIS VALUE MAY CHANGE. |
| | |
| | 6) NOTE: NO, SEE THE MASTER PERMIT # FOR THE BUILDING |
| | WAS REMOVED FROM BEING REFERENCE IN OUR SYSTEM AND |
| | NOTES WERE ADDED THAT A NEW RECORD NOC WAS NEEDED. |
| | PLEASE KNOW THIS IS REQUIRED BEFORE PICKING UP PERMIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW THIS INTERIOR BUILD OUT WILL REQUIRE A NEW |
| | NOTICE OF COMMENCEMENT AS THE ONE UNDER THE BUILDING |
| | HAS EXPIRED AND IS NOT PART OF THIS SCOPE OF WORK. FS |
| | 713.13 |
| | |
| | 7) NOTE:OK, HOWEVER SEE LOAD CALCULATIONS AS |
| | SUBMITTED DO NOT CORRELATE WITH PANEL SCHEDULE. |
| | PLEASE ALSO SEE WHEN THE RECEPT LOADS ARE KNOWN, PLEASE |
| | SEE 220.13. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE AND SHOW ON LOAD SUMMARY AND |
| | CALCULATIONS ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4). PLEASE |
| | DETAIL ALL NEW HORNS AND STROBES AT THE MINIMUM LEVELS |
| | AS REQUIRED IN CHAPTER 11 OF THE 2004 FBC. |
| | THIS WAS NOT NOTED IN PREVIOUS REVIEW AS IT HAS NOW |
| | BECOME AN ELECTRICAL REVIEW ITEM TO BE REVIEWED FOR. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS. PLEASE SEE THIS ONLY BEING GIVEN AS A |
| | NOTICE AT THIS TIME. |
| | |
| | ** PLEASE KNOW, AS PLANS FOR MANY ITEMS WILL CHANGE, |
| | ALL NOTES MAY NOT BE COMPLETE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |