Text |
| 2006-10-13 09:17:08 | **** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE |
| | WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER |
| | THE 2004 FBC. PLEASE ADJUST AS NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE ALL AREAS WHICH ARE BEING SHOWN AS |
| | "COMMON AREAS" MAY NOT BE FED FROM PANELS WHICH ARE FOR |
| | TENANT SPACE.210.25 |
| | |
| | 3) NOTE: PLEASE SEE ELECTRICAL PANELS MAY NOT BE IN |
| | RATED EXIT CORRIDOR SEE FBC BUILDING REVIEW COMMENTS. |
| | IF INDEED THIS IS GOING TO BE TWO TENANT SPACES PLEASE |
| | VERIFY AS ONLY ONE METER IS BEING SHOWN AND MAY NOT |
| | FEED TWO TENANTS/SEPARATE OCCUPANCIES FROM ONE |
| | METER/MAIN. |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWS WHICH MAY AFFECT |
| | THE AMOUNT OF TENANTS ALLOWED PER FLOOR , CORRIDORS |
| | ETC. |
| | PLEASE SEE PREVIOUS NOTE WITHE RESPECT TO THE COMMON |
| | AREA NOT BEING FED OR CONTAINING THE ELECTRICAL FROM |
| | TENANT PANEL. |
| | |
| | 4) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A |
| | INSTA-HOT., YET COULD NOT FIND THIS ON PLANS.PLEASE SEE |
| | 430.30, 430.31 ETC AS LOAD OF THIS SIZE WHEN UNIT IS |
| | REQUIRED TO CONTAIN A DISCONNECT , A PLUG MAY NOT BE |
| | USED. PLEASE ALSO VERIFY IF THE DISCONNECTING MEANS |
| | CONTAINS OCP, IF SO ,PLEASE SEE 110.26. |
| | |
| | 4) NOTE:PLEASE PROVIDE SPECIFIC ROOMS AND AREAS ON |
| | PANEL SCHEDULE WHICH WILL CORRELATE WITH THE PLANS AND |
| | LAYOUT. 408.6, PLEASE ALSO BE SURE TO INDICATE ALL |
| | CONDUCTOR SIZES ON PANEL SCHEDULE. |
| | 310.16, 240.4 |
| | FBC 106.1.2. |
| | |
| | 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| | SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF |
| | OWNER SUPPLIED. |
| | FBC 108.3 |
| | PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES |
| | BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE |
| | OWED. |
| | PLEASE KNOW, ONCE THE SQ FT HAS BEEN VERIFIED FOR |
| | ACTUAL SCOPE OF WORK, THIS VALUE MAY CHANGE. |
| | |
| | 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL |
| | REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UNDER |
| | THE BUILDING HAS EXPIRED AND IS NOT PARTOF THIS SCOPE |
| | OF WORK. FS 713.13 |
| | |
| | 7) NOTE: PLEASE INDICATE AND SHOW ON LOAD SUMMARY AND |
| | CALCULATIONS ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 |
| | |
| | ** PLEASE KNOW, AS PLANS FOR MANY ITEMS WILL CHANGE , |
| | ALL NOTES MAY NOT BE COMPLETE AT THIS TIME. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |