| 2007-04-25 18:01:04 | ** UNSAT 3RD REVIEW ** |
| | |
| | |
| | ***** PLEASE SEE THE PLANS HAVE NOW BEEN REVISED |
| | REMOVING MANY CODE COMPLIANT ITEMS WHICH WERE OK ON |
| | PREVIOUS PLANS???? |
| | PLEASE SEE THERE ARE SEVERAL ITEMS WHICH WERE ON PLANS |
| | WHICH HAVE NOW BEEN REMOVED. |
| | IT IS UNCLEAR WHY SO MANY OF THESE ITEMS WERE REMOVED |
| | OR CHANGED FROM PREVIOUS PLANS WHICH WERE SUBMITTED ON |
| | THE FIRST REVIEW. |
| | |
| | ** ONE COPY OF EACH WAS RETAINED BY THIS OFFICE. |
| | |
| | 1) NOTE: PLEASE INDICATE THE AIC RATINGS ON PLANS AS |
| | PREVIOUSLY SHOWN. |
| | 110.9 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE MISSING RECEPTACLE FOR MASTER |
| | BEDROOM 2FT OR MORE OF WALL PER 210.52 |
| | |
| | 3) NOTE: PLEASE SEE MISSING DESIGNATIONS ON PANEL |
| | SCHEDULE AS PREVIOUSLY DONE ON PANEL SCHEDULE. PLEASE |
| | SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY FROM THE |
| | NEC> |
| | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 4) NOTE: PLEASE SEE THE KW RATING WHICH IS 7KW ON |
| | MECHANICAL PLANS IS NOW SHOWN AS 6.5KW ON ELECTRICAL |
| | PLANS.?? |
| | PLEASE COORDINATE. |
| | 424.3, 310.16, 240.4 ETC. |
| | |
| | 5) NOTE: PLEASE SEE MISSING AFCI NOTE WHICH MENTIONS |
| | ALL REQUIRED PROTECTED OUTLETS IN BEDROOMS PER 210.12. |
| | (PREVIOUS PLANS NOTES WERE OK) |
| | |
| | 6) NOTE: PLEASE SEE MISSING REQUIRED CODES TO BE STATED |
| | ON ELECTRICAL PLANS AS PREVIOUSLY DONE. |
| | NFPA-70 2002 |
| | NFPA-72 2002 |
| | THE 2004 FBC. |
| | |
| | 7) NOTE: PLEASE SEE MISSING GFI FOR CU OUTSIDE PER |
| | 210.8, 210.63 |
| | |
| | 8) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER HEATER |
| | PER 422.31. |
| | THIS MENTIONS *HARD-WIRED* WHICH IS REQUIRED PER THE |
| | NEC ALSO, HOWEVER THE SYMBOL USED FOR THIS IS A |
| | RECEPTACLE?? |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |