| 2007-01-19 07:23:42 | |
| | |
| | |
| | *** UNSAT 2ND REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE THE EXACT SAME PLANS WHICH WERE |
| | PREVIOUSLY SUBMITTED ARE SUBMITTED BACK WITH OUT |
| | CORRECTIONS MADE. |
| | PLEASE SEE ONE SET HAS SOME HAND DRAWN CHANGES WHICH |
| | ARE NOT PERMITTED TO PLANS WHICH ARE SIGNED, DATED AND |
| | SEALED BY AN ARCHITECT OR ENGINEER. PLEASE GIVE PLANS |
| | BACK TO THE DESIGN PROFESSIONAL, SHEETS WILL BE |
| | REQUIRED TO BE RE-PRINTED AND SIGNED DATED AND SEALED |
| | AS PREVIOUSLY DONE. |
| | PLEASE SEE THE COMMENTS FROM THE PREVIOUS REVIEW ARE |
| | STILL ATTACHED TO PACKAGE. |
| | |
| | 2) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE |
| | SOUTHERN SECTION MEETING IN OCT 06WHERE WE WERE |
| | DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE |
| | DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| | ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| | THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| | SA/SMOKE ALARMS. |
| | THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| | OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| | SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| | FOR OTHER NEW HOMES. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | PLANS ARE BEING CORRECTED FOR OTHER ITEMS, PLEASE MAKE |
| | THIS ADJUSTMENT. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | ** TAKEN FROM THE NFPA-72** |
| | 11.5.1.1 SMOKE DETECTION.WHERE REQUIRED BY APPLICABLE |
| | LAWS, CODES, OR STANDARDS FOR THE SPECIFIED OCCUPANCY, |
| | APPROVED SINGLE- AND MULTIPLE-STATION SMOKE ALARMS |
| | SHALL BE INSTALLED AS FOLLOWS: |
| | (1)IN ALL SLEEPING ROOMS |
| | EXCEPTION:SMOKE ALARMS SHALL NOT BE REQUIRED IN |
| | SLEEPING ROOMS IN EXISTING ONE- AND TWO-FAMILY DWELLING |
| | UNITS. |
| | (2)OUTSIDE OF EACH SEPARATE SLEEPING AREA, IN THE |
| | IMMEDIATE VICINITY OF THE SLEEPING ROOMS |
| | (3)ON EACH LEVEL OF THE DWELLING UNIT, INCLUDING |
| | BASEMENTS |
| | EXCEPTION:IN EXISTING ONE- AND TWO-FAMILY DWELLING |
| | UNITS, APPROVED SMOKE ALARMS POWERED BY BATTERIES SHALL |
| | BE PERMITTED. |
| | 11.5.1.2 NOTIFICATION. |
| | (A) FIRE-WARNING EQUIPMENT FOR DWELLING UNITS SHALL |
| | PROVIDE A SOUND THAT IS AUDIBLE IN ALL OCCUPIABLE |
| | DWELLING AREAS. |
| | (B) WHERE MORE THAN ONE SMOKE OR HEAT ALARM IS |
| | INSTALLED FOR NEW CONSTRUCTION, THEY SHALL BE ARRANGED |
| | SO THAT THE OPERATION OF ANY SMOKE OR HEAT ALARM CAUSES |
| | THE ALARM IN ALL SMOKE AND HEAT ALARMS WITHIN THE |
| | DWELLING UNIT TO SOUND |
| | |
| | 11.8.3* SMOKE DETECTORS AND SMOKE ALARMS. SMOKE ALARMS, |
| | SMOKE DETECTORS, DEVICES, COMBINATION OF DEVICES, AND |
| | EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER'S LISTING AND INSTRUCTIONS, AND UNLESS |
| | SPECIFICALLY LISTED FOR THE APPLICATION, SHALL COMPLY |
| | WITH REQUIREMENTS IN11.8.3.1 THROUGH11.8.3.5. |
| | |
| | 3) NOTE: PLEASE SEE COPY OF FLORIDA STATUTES |
| | 553.80(2)(B) WITH RESPECT TO REPEAT NOTES FOR CODE |
| | COMPLIANCE. THIS IS BEING GIVEN ONLY AS NOTICE AT THIS |
| | TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |