| Date |
Text |
| 2006-10-06 00:00:00 | **** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SEE FAC 61G17 AND FS |
| | 472.025 AS THE SURVEY'S ARE REQUIRED TO |
| | BE SEALED WHEN SIGNED TO BE VALID. |
| | |
| | 2) NOTE: PLEASE SEE ALL SEALS ON PLANS |
| | SHALL BE CLEAR AND VISABLE WITH ALL |
| | INFORMATION ON SAID SEAL AS REQUIRED PER |
| | FAC 61G1-16.003, FS 481.221 |
| | |
| | 3) NOTE: PLEASE SEE MISSING DINING |
| | AREA/BREAKFEST AREAS AND THE LIKE FOR |
| | CIRCUTING AND MIN 20A #12 CIRCUITS |
| | REQUIRED TO MEET 210.52B1, 220.16, |
| | 210.11C1 |
| | |
| | 4) NOTE: PLEASE OCP ON 50A RANGE RECEPT |
| | SHALL NOT EXCEED RATINGS AS PERMITTED IN |
| | TABLES 220.21B3 |
| | |
| | 5) NOTE: PLEASE SEE OCP FOR AHU, SHALL |
| | MEET 424.3B FOR MIN 125%. |
| | PLEASE ADJUST. |
| | |
| | 2) NOTE: PLEASE LIST THE OCP FOR THE |
| | BRANCH CIRCUIT TO THE CU. |
| | |
| | |
| | PLEASE SEE NOTES ONE AND TWO ARE |
| | REQUIRED FOR ALL. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |