Plan Review Notes
Plan Review Notes For Permit 06100075
Permit Number 06100075
Review Stop P
Sequence Number 8
Notes
Date Text
2008-04-12 08:16:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
  
 2. SHTS A-2, 2 0F 3 & A-3, 3 OF 3 STILL SHOW THE BREAK
 ROOM SINK AND SHT A-3 STILL SHOWS THE BREAK ROOM SINK
 DETAILS. PLEASE REVISE ALL SHEETS WITH THE BREAK ROOM
 SINK SHOWN. DELETE THE SINK REFERENCES TO REFLECT
 REVISION. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT DURING OUR CONVERSATION WITH
 THE REPRESTATIVE OF ARCHITECT G. RAYMOND BERRY, IT WAS
 INDICATED THAT IF THE WORK OF THE ENGINEER WAS TO BE
 TAKEN OVER BY THE NEW ARCHITECT, THEN ALL WORK BY THE
 ENGINEER SHALL BE RESUBMITTED. THIS WILL INCLUDE THE
 MECHANICAL SHEETS AND THE FIRE SPRINKLER SHEETS.
  
 3. SHT P1 PLUMBING RISER BREAK AREA DOES NOT MEET CODE
 REQUIREMENTS. AS SHOWN THERE IS NO TRAP FOR THE ICE
 MAKER, AND THE ICE MAKER SHALL BE INDIRECTLY CONNECTED
 TO THE SANITARYSYSTEM NOT DIRECT CONNECTION AS SHOWN.
 SECTIONS 802.1.1 & 1002.1. A FLOOR SINK OR HUB DRAIN IS
 REQUIRED. SECTIONS 802.3 & 802.3.2.
 ****RESPONSE NOTED, BUT NO AIR GAP IS SHOWN ON THE
 RISER DIAGRAM. THE PIPING FROM THE ICE MAKER IS
 DIRECTLY CONNECTED TO THE STANDPIPE.
  
 4. SHT P1 WATER RISER DIAGRAM. A WATER HAMMER ARRESTOR
 IS REQIRED AT THE ICE MACHINE PER SECTION 604.9. PLEASE
 INDICATE ON THE WATER RISER DIAGRAM. THE WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE", NOT IN THE CEILING. PDI-WH 201.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR IS
 SHOWN ON THE SANITARY RISER DIAGRAM, NOT ON THE WATER
 LINE TO THE ICE MAKER AS REQUIRED.
  
 5. ALL SHEETS. THE ADDRESS FOR THE ARCHITECT DOES NOT
 RELFECT THE ADDRESS OF RECORD ON THE FLORIDA STATE DBPR
 WEBSITE. (SEE ATTACHED SHEET). PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS SO THEY CORRELATE. FAC
 61G1-16.004(1) & FS 481.2055.
 ****RESPONSE NOTED, BUT THE ADDRESS ON THE TITLE BLOCKS
 STILL DO NOT REFLECT THE STATE OF FLORIDA DBPR WEBSITE.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  