Review Stop E
Sequence Number 7
Notes
Date Text
2007-12-24 08:19:15** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE THE WATTAGE IN CALCULATIONS SHALL
 BE BASED ON THE MAXIMUM WATTAGE PER MANUFACTURE LABEL
 ON FIXTURE.
 PLEASE SEE FOR ONE EXAMPLE, THE 100W PENDANTS INDICATE
 40W BULBS, HOWEVER THIS IS ONE EXAMPLE OF THE WHERE BY
 PLACING A LOWER WATTAGE BULB IN FIXTURE DOES NOT ALLOW
 LESS WATTAGE USE. THE SAME IS FOR ALL FIXTURES.
 13-415.2.ABC.1.2(1)
  
 2) NOTE: PLEASE SEE THE SEPARATE SHEETS SHOWING
 LIGHTING CALCULATIONS REQUIRE TITLE BLOCKS PER FAC
 61G1-16.004
  
 3) NOTE: PLEASE SEE THESE WERE BROUGHT BACK IN AS A
 SUBMITTAL WHEN IN FACT THESE ARE REVISIONS. PLEASE SEE
 THE FEE OF $70 IS DUE.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  