Plan Review Notes
Plan Review Notes For Permit 06100075
Permit Number 06100075
Review Stop E
Sequence Number 6
Notes
Date Text
2007-12-10 08:24:41**** DENIED REVISION ****
  
 1) NOTE: PLEASE SEE THE METHOD BEING SUBMITTED MAY NOT
 BE USED ON AN EXISTING BUILDING WHEN ALL COMPONENTS ARE
 NOT NEW OR NEW BEING INSTALLED. PLEASE KNOW THE
 MECHANICAL REVIEWER WILL LOOK AT OTHER SYSTEMS ALONG
 WITH THE BUILDING REVIEWER.
 IF THE *WHOLE* BUILDING BY DEFINITION IS NOT BEING
 DONE THEN METHOD *A* MAY NOT BE USED.
 PLEASE SEE FBC 13-415.2.B, 13-101.1.3. PLEASE SEE
 13-101.1.6 WHEN ALL ARE KNOWN OR NEW. THIS WAS
 CONFIRMED WITH THE FLORIDA BUILDING COMMISSION ON SEPT
 26, 2007.
 PLEASE ALSO KNOW THE VERSION AS SUBMITTED IS FROM THE
 ADOPTION OF THE 2006 REVISIONS TO THE FLORIDA BUILDING
 CODE WHICH DID NOT GO INTO EFFECT UNTIL DECEMBER 8TH,
 2006. PLEASE KNOW THIS PROJECT WAS APPLIED FOR PERMIT
 BEFORE THIS DATE WHICH PLACES THE VERSION UNDER THE
 2.11.
 PLEASE SEE IN EITHER CASE THE FIXTURE LEGEND ON PLANS
 IS NOT COMPLETE AT THIS TIME. PLEASE SEE THE INPUT DATA
 REPORT ALSO DOES NOT CORRELATE WITH THE PLANS AS
 SUBMITTED. THE FIXTURE LEGEND MUST BE COMPLETE WITH ALL
 FIXTURE INFORMATION ON PLANS IN ORDER TO REVIEW THE
 INPUT DATA REPORT FOR ACCURATE REVIEW.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING.
 **
 PLEASE ALSO SEE 13-413.1.ABC.2.1 AND .2.2. THIS IS A
 NEW COMMENT AS THIS IS NOW KNOWN TO THIS OFFICE THAT
 NOTES ARE REQUIRED ON PLANS ACCORDINGLY.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]