| 2007-11-04 09:31:37 | 2007-11-4 09:31:37 |
| | |
| | ** DENIED 2ND REVIEW OF REVISIONS** |
| | |
| | ** PLEASE SEE THERE ARE STILL ITEMS FROM PREVIOUS |
| | REVIEW ALONG WITH SOME NEW COMMENTS DUE TO CHANGES ON |
| | PLANS/DOCUMENTS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE ENERGY CALCULATIONS AS SUBMITTED |
| | ARE FROM THE 2001 CODE. THESE MAY NOT BE USED AS THE |
| | PERMIT APPLICATION WAS MADE AFTER OCT 1ST, 2005. PLEASE |
| | KNOW AS PERMIT APPLICATION DATE WAS ALSO BEFORE THE |
| | MOST RECENT CODE CHANGE, THE VERSION IS 2004, 2.11. THE |
| | METHOD IS BASED ON ACTUAL SCOPE OF WORK. AS STATED |
| | PREVIOUSLY PLEASE SEE 13-415.2 AS PERFORMANCE |
| | CALCULATIONS FOR TRACK LIGHTING USE REALLY NEEDS TO BE |
| | LOOKED AT. PLEASE SEE THE METHOD AND PRESCRIPTIVE |
| | REQUIREMENTS. |
| | 13-415.1.B, 13-415.2.ABC.1.2 ETC. |
| | THE NEWER VERSION CONTAINS SEVERAL CHANGES. |
| | |
| | 2) NOTE: PLEASE SEE 210.12 FOR TRACK LIGHTING |
| | CALCULATIONS REQUIRED FOR NEC MINIMUM CODE COMPLIANCE. |
| | |
| | 3) NOTE: PLEASE SEE THE NEW GFI RECEPTACLES WERE ADDED |
| | PRE PREVIOUS NOTE, HOWEVER MISSING CIRCUITING. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS AS |
| | MENTIONED AS NO LOW VOLTAGE PERMITS TO DATE HAVE BEEN |
| | APPLIED FOR THE SCOPE OF WORK AS SHOWN ON PLANS. |
| | |
| | 5) NOTE: PLEASE SEE THE LETTER AS SUBMITTED FOR CHANGE |
| | IN ARCHITECT IS NOT ACCEPTABLE. THIS IS THE SAME LETTER |
| | AS PREVIOUSLY SUBMITTED. |
| | PLEASE SEE THE GUIDELINES AS SET-FORTH IN THE FAC |
| | 61G1. |
| | PLEASE KNOW THE LETTER NEEDS TO ORIGINAL SIGNED, DATED |
| | AND SEALED. |
| | THE LETTER IS ALSO NOT NOTARIZED CORRECTLY PER FS |
| | 117.05. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |