Plan Review Notes
Plan Review Notes For Permit 06100075
Permit Number 06100075
Review Stop E
Sequence Number 5
Notes
Date Text
2007-11-04 09:31:372007-11-4 09:31:37
  
 ** DENIED 2ND REVIEW OF REVISIONS**
  
 ** PLEASE SEE THERE ARE STILL ITEMS FROM PREVIOUS
 REVIEW ALONG WITH SOME NEW COMMENTS DUE TO CHANGES ON
 PLANS/DOCUMENTS SUBMITTED.
  
 1) NOTE: PLEASE SEE ENERGY CALCULATIONS AS SUBMITTED
 ARE FROM THE 2001 CODE. THESE MAY NOT BE USED AS THE
 PERMIT APPLICATION WAS MADE AFTER OCT 1ST, 2005. PLEASE
 KNOW AS PERMIT APPLICATION DATE WAS ALSO BEFORE THE
 MOST RECENT CODE CHANGE, THE VERSION IS 2004, 2.11. THE
 METHOD IS BASED ON ACTUAL SCOPE OF WORK. AS STATED
 PREVIOUSLY PLEASE SEE 13-415.2 AS PERFORMANCE
 CALCULATIONS FOR TRACK LIGHTING USE REALLY NEEDS TO BE
 LOOKED AT. PLEASE SEE THE METHOD AND PRESCRIPTIVE
 REQUIREMENTS.
 13-415.1.B, 13-415.2.ABC.1.2 ETC.
 THE NEWER VERSION CONTAINS SEVERAL CHANGES.
  
 2) NOTE: PLEASE SEE 210.12 FOR TRACK LIGHTING
 CALCULATIONS REQUIRED FOR NEC MINIMUM CODE COMPLIANCE.
  
 3) NOTE: PLEASE SEE THE NEW GFI RECEPTACLES WERE ADDED
 PRE PREVIOUS NOTE, HOWEVER MISSING CIRCUITING.
 FBC 106.1.2 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS AS
 MENTIONED AS NO LOW VOLTAGE PERMITS TO DATE HAVE BEEN
 APPLIED FOR THE SCOPE OF WORK AS SHOWN ON PLANS.
  
 5) NOTE: PLEASE SEE THE LETTER AS SUBMITTED FOR CHANGE
 IN ARCHITECT IS NOT ACCEPTABLE. THIS IS THE SAME LETTER
 AS PREVIOUSLY SUBMITTED.
 PLEASE SEE THE GUIDELINES AS SET-FORTH IN THE FAC
 61G1.
 PLEASE KNOW THE LETTER NEEDS TO ORIGINAL SIGNED, DATED
 AND SEALED.
 THE LETTER IS ALSO NOT NOTARIZED CORRECTLY PER FS
 117.05.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
2007-11-04 09:10:302007-11-04 09:10:30
  
 IN ELECTRIC FOR REVIEW, WILL BE ROUTED BACK TO INCOMING
 ONCE REVIEW IS DONE.