2007-12-06 08:34:10****CORRECTIONS****
 ****REVISION DATED 12/4/7****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.THE ARCHITECT'S RESPONSE TO THE PREVIOUS CORRECTION
 LIST REGARDING ENERGY CALC AREA OF 2653 NOT CORRELATING
 WITH THE SQUARE FOOT AREA ON THE PLAN OF 2910 IS NOTED.
 ARCHITECT STATES THAT THIS IS THE DIFFERENCE BETWEEN
 GROSS VS. NET.SEE FBC TABLE 1004.1.2, MERCANTILE
 OCCUPANT LOAD IS TO BE BASED ON GROSS, NOT NET.AT
 2910/30 (STORES FIRST FLOOR, SEE FBC TABLE 1004),
 OCCUPANT LOAD SHOULD BE 97, NOT 49 AS SHOWN ON THE
 PLAN.ENERGY CALCS AREA IS TO BE OUTSIDE WALL TO
 OUTSIDE WALL, SEE FBC13-202, DEFINITION OF GROSS FLOOR
 AREA.IF BUILDING AREA AND ENERGY CALCS BOTH REQUIRE
 GROSS AREA, THEY SHOULD BE THE SAME. ALSO PLEASE REVISE
 OCCPUANT LOAD ON THE PLAN.
  
  