2007-08-01 18:54:16** UNSAT **
  
  
 1) NOTE: PLEASE REVISE AND UPDATE ENERGY CALCULATIONS
 TO COORDINATE WITH PLANS.
 PLEASE SEE THE METHOD OF CONTROL NEED TO CORRELATE WITH
 PLANS. THIS CAN NOT BE *MANUAL ON/OFF* WHEN AUTOMATED
 MEANS IS BEING SHOWN ON PLANS.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOAD IN
 ENERGY CALCULATIONS.
 13-415.1.A, 13-415.2
 PLEASE SPECIFY THE MAXIMUM TIMES ON DEVICES FOR OVER
 RIDES.
  
 2) NOTE: PLEASE SEE THE PLANS ARE MISSING GFI
 RECEPTACLES FOR OUTSIDE CONDENSING UNITS. 210.63,
 210.8B
  
 3) NOTE: PLEASE SEE CIRCUITS IN PANEL NEED TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. PLEASE
 SEE 408.4. PLEASE ALSO SEE THE FOLLOWING WHICH IS
 EXTRACTED FROM THE CODE COMMENTARY.
 * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4,
 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE AHU IN PANEL ?C? WHICH CONTAINS #8
 ON A 60AMP BREAKER. THE CONDUCTORS ARE NOT LARGE
 ENOUGH. 240.4,310.16.
  
 5) NOTE: PLEASE SEE THE RISER AS THIS IN SHOWING A
 2200AMP DESIGNATION FOR METERS. THIS MUST BE A
 MISPRINT.
 FBC 106.1.2
  
 6) NOTE: PLEASE KNOW THAT NO LOW VOLTAGE PERMIT HAS
 BEEN APPLIED FOR TO DATE FOR THE LOW VOLTAGE SCOPE OF
 WORK AS SHOWN ON PLANS.
 PLEASE KNOW THIS IS REQUIRED TO BE SEPARATE PERMIT,
 SEPARATE FEE.
  
 7) NOTE: PLEASE BE SURE THE LETTER SUBMITTED FOR CHANGE
 IN DESIGN PROFESSIONAL OF RECORD IS NOTARIZED. PLEASE
 SEE THE FS 117.05 GIVES THE SPECIFICS ON CORRECT NOTARY
 INFORMATION REQUIRED ON PLANS.
 PLEASE CLARIFY IF THE DESIGNER OF RECORD WHO SIGNED,
 DATED AND SEALED ENERGY CALCULATIONS IS STILL THE
 DESIGNER OF RECORD.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved