| 2007-08-01 18:54:16 | ** UNSAT ** |
| | |
| | |
| | 1) NOTE: PLEASE REVISE AND UPDATE ENERGY CALCULATIONS |
| | TO COORDINATE WITH PLANS. |
| | PLEASE SEE THE METHOD OF CONTROL NEED TO CORRELATE WITH |
| | PLANS. THIS CAN NOT BE *MANUAL ON/OFF* WHEN AUTOMATED |
| | MEANS IS BEING SHOWN ON PLANS. |
| | PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOAD IN |
| | ENERGY CALCULATIONS. |
| | 13-415.1.A, 13-415.2 |
| | PLEASE SPECIFY THE MAXIMUM TIMES ON DEVICES FOR OVER |
| | RIDES. |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS ARE MISSING GFI |
| | RECEPTACLES FOR OUTSIDE CONDENSING UNITS. 210.63, |
| | 210.8B |
| | |
| | 3) NOTE: PLEASE SEE CIRCUITS IN PANEL NEED TO BE |
| | SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. PLEASE |
| | SEE 408.4. PLEASE ALSO SEE THE FOLLOWING WHICH IS |
| | EXTRACTED FROM THE CODE COMMENTARY. |
| | * CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* 408.4, |
| | 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 4) NOTE: PLEASE SEE AHU IN PANEL ?C? WHICH CONTAINS #8 |
| | ON A 60AMP BREAKER. THE CONDUCTORS ARE NOT LARGE |
| | ENOUGH. 240.4,310.16. |
| | |
| | 5) NOTE: PLEASE SEE THE RISER AS THIS IN SHOWING A |
| | 2200AMP DESIGNATION FOR METERS. THIS MUST BE A |
| | MISPRINT. |
| | FBC 106.1.2 |
| | |
| | 6) NOTE: PLEASE KNOW THAT NO LOW VOLTAGE PERMIT HAS |
| | BEEN APPLIED FOR TO DATE FOR THE LOW VOLTAGE SCOPE OF |
| | WORK AS SHOWN ON PLANS. |
| | PLEASE KNOW THIS IS REQUIRED TO BE SEPARATE PERMIT, |
| | SEPARATE FEE. |
| | |
| | 7) NOTE: PLEASE BE SURE THE LETTER SUBMITTED FOR CHANGE |
| | IN DESIGN PROFESSIONAL OF RECORD IS NOTARIZED. PLEASE |
| | SEE THE FS 117.05 GIVES THE SPECIFICS ON CORRECT NOTARY |
| | INFORMATION REQUIRED ON PLANS. |
| | PLEASE CLARIFY IF THE DESIGNER OF RECORD WHO SIGNED, |
| | DATED AND SEALED ENERGY CALCULATIONS IS STILL THE |
| | DESIGNER OF RECORD. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |