Plan Review Notes
Plan Review Notes For Permit 06100075
Permit Number 06100075
Review Stop B
Sequence Number 3
Notes
Date Text
2007-09-11 19:33:50PROJECT: 1970 SOUTH DIXIE HIGHWAY/UNIT C-2/REVISIONS
  
 REVIEW: 2004 FLORIDA EXISTING BUILDING CODE W/ 2006
 REVS
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) PLEASE INDICATE THE LEVEL OF ALTERATION AS PER THE
 FOLLOWING:
  
 301.5 . A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO SECTION
 303,304 & 305 OF THIS CODE.
  
 2) PLEASE PROVIDE PROOF OF ORIGINAL DESIGNER
 NOTIFICATION AS PER THE FOLLOWING :
  
 61G15-27.001 PROCEDURES FOR A SUCCESSOR PROFESSIONAL
 ENGINEER ADOPTING AS HIS OWN THE WORK OF ANOTHER
 ENGINEER.
 (1) A SUCCESSOR PROFESSIONAL ENGINEER SEEKING TO REUSE
 ALREADY SEALED CONTRACT DOCUMENTS UNDER THE SUCCESSOR
 PROFESSIONAL ENGINEER'S SEAL MUST BE ABLE TO DOCUMENT
 AND PRODUCE UPON REQUEST EVIDENCE THAT HE HAS IN FACT
 RECREATED ALL THE WORK DONE BY THE ORIGINAL
 PROFESSIONAL ENGINEER. IN OTHER WORDS, CALCULATIONS,
 SITE VISITS, RESEARCH AND THE LIKE MUST BE DOCUMENTED
 AND PRODUCEABLE UPON DEMAND. FURTHER, THE SUCCESSOR
 PROFESSIONAL ENGINEER MUST TAKE ALL PROFESSIONAL AND
 LEGAL RESPONSIBILITY FOR THE DOCUMENTS WHICH HE SEALED
 AND SIGNED AND CAN IN NO WAY EXEMPT HIMSELF FROM SUCH
 FULL RESPONSIBILITY. PLANS NEED NOT BE REDRAWN BY THE
 SUCCESSOR PROFESSIONAL ENGINEER; HOWEVER, JUSTIFICATION
 FOR SUCH ACTION MUST BE AVAILABLE THROUGH WELL KEPT AND
 COMPLETE DOCUMENTATION ON THE PART OF THE SUCCESSOR
 PROFESSIONAL ENGINEER AS TO HIS HAVING RETHOUGHT AND
 REWORKED THE ENTIRE DESIGN PROCESS. A SUCCESSOR
 PROFESSIONAL ENGINEER MUST USE HIS OWN TITLE BLOCK,
 SEAL AND SIGNATURE AND MUST REMOVE THE TITLE BLOCK,
 SEAL AND SIGNATURE OF THE ORIGINAL PROFESSIONAL
 ENGINEER BEFORE REUSING ANY SEALED CONTRACT DOCUMENTS.
 (2) PRIOR TO SEALING AND SIGNING WORK A SUCCESSOR
 PROFESSIONAL ENGINEER SHALL BE REQUIRED TO NOTIFY THE
 ORIGINAL PROFESSIONAL ENGINEER, HIS SUCCESSORS, OR
 ASSIGNS BY CERTIFIED LETTER TO THE LAST KNOWN ADDRESS
 OF THE ORIGINAL PROFESSIONAL ENGINEER OF THE
 SUCCESSOR'S INTENTION TO USE OR REUSE THE ORIGINAL
 PROFESSIONAL ENGINEER'S WORK. THE SUCCESSOR
 PROFESSIONAL ENGINEER WILL TAKE FULL RESPONSIBILITY FOR
 THE DRAWING AS THOUGH THEY WERE THE SUCCESSOR
 PROFESSIONAL ENGINEER'S ORIGINAL PRODUCT.
 SPECIFIC AUTHORITY 471.033(2) FS. LAW IMPLEMENTED
 471.033(1)(J), 471.005(6) FS. HISTORY?NEW 8-25-87,
 AMENDED 4-21-88, 8-3-88, FORMERLY 21H-27.001.
  
 3) PLEASE PROVIDE DETAILED UL/GA ASSEMBLY FOR TS COLUMN
 FIRE PROTECTION. REQUIRE
 EXACT DETAIL/FILE NUMBER AS LISTED.
  
 4) PLEASE INDICATE THE EXISTING TESTED ASSEMBLY NUMBER
 USED FOR THE TENANT SEPARATION AT THE EXISTING
 MERCHANTILE SEPARATION.
  
 5) ON THE EXISTING PLAN, SHEET A-1, THE ENTRY DOORS ARE
 NOT DESIGNATED FOR USE AT FLOOR AREAS 1 AND 3; THE
 REVISED SHEET A-1 DOES NOT REFLECT THIS. PLEASE
 CLARIFY.
  
 6) PLEASE PROVIDE FIRE-STOPPING DETAILS FOR ALL
 FLOOR/WALL/CEILING THROUGH PENETRATIONS:
  
 712.3.1.2 THROUGH-PENETRATION FIRESTOP
 SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 7) ALL FINISH BASE TRIM SHALL COMPLY WITH THE
 FOLLOWING:
  
 1210.1 FLOORS.
 IN OTHER THAN DWELLING UNITS, TOILET AND BATHING
 ROOM FLOORS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE THAT EXTENDS UPWARD ONTO THE WALLS AT LEAST 6
 INCHES (152 MM).
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
 E-MAIL: [email protected]
  
  
  
  
  
  
  