| Notes |
| Date |
Text |
| 2007-12-22 09:01:11 | MECHANICAL PLANS NOT BEING REVISED AT THIS TIME. NEW | | | METHOD A ENERGY CALCULATIONS HAVE BEEN SUBMITTED. AS AN | | | EXISTING BUILDING WHERE THE SCOPE OF WORK IS NOT THE | | | ENTIRE BUILDING AND DOES NOT MEET THE DEFINITION OF A | | | RENOVATION, METHOD A IS NOT ACCEPTABLE FOR | | | DEMONSTRATING COMPLIANCE WITH FBC CHAPTER 13. SEE FBC | | | 13-400.0.C.4. FOR MECHANICAL THE ONLY REQUIREMENT IS | | | MINIMUM PRESCRIPTIVE EFFICIENCIES IN ACCORDANCE WITH | | | THIS SECTION AND FBC 13-101.6. THAT HAS ALREADY BEEN | | | DEMONSTRATED ON PLANS AND PLANS ARE COMPLIANT. | | | THEREFORE THE METHOD A CALCULATIONS PROVIDED WITH THIS | | | REVISION HAVE NOT BEEN REVIEWED OR CONSIDERED AS PART | | | OF THIS PERMIT FOR MECHANICAL. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|