Plan Review Notes
Plan Review Notes For Permit 06100075
Permit Number 06100075
Review Stop M
Sequence Number 2
Notes
Date Text
2007-12-22 09:01:11MECHANICAL PLANS NOT BEING REVISED AT THIS TIME. NEW
 METHOD A ENERGY CALCULATIONS HAVE BEEN SUBMITTED. AS AN
 EXISTING BUILDING WHERE THE SCOPE OF WORK IS NOT THE
 ENTIRE BUILDING AND DOES NOT MEET THE DEFINITION OF A
 RENOVATION, METHOD A IS NOT ACCEPTABLE FOR
 DEMONSTRATING COMPLIANCE WITH FBC CHAPTER 13. SEE FBC
 13-400.0.C.4. FOR MECHANICAL THE ONLY REQUIREMENT IS
 MINIMUM PRESCRIPTIVE EFFICIENCIES IN ACCORDANCE WITH
 THIS SECTION AND FBC 13-101.6. THAT HAS ALREADY BEEN
 DEMONSTRATED ON PLANS AND PLANS ARE COMPLIANT.
 THEREFORE THE METHOD A CALCULATIONS PROVIDED WITH THIS
 REVISION HAVE NOT BEEN REVIEWED OR CONSIDERED AS PART
 OF THIS PERMIT FOR MECHANICAL.
  