Plan Review Notes
Plan Review Notes For Permit 06100075
Permit Number 06100075
Review Stop E
Sequence Number 1
Notes
Date Text
2006-10-12 19:54:52*** UNSAT ***
  
 1) NOTE:PLEASE CORRELATE VOLTAGE FOR A/C SYSTEMS,.
 PLEASE SEE MECH PLANS INDICATE 208V AND ELECTRICAL
 PLANS INDICATE 240 V.
  
 2) NOTE: PLEASE SEECONDUCTOR SIZES FOR AHU #2, PLEASE
 SEE , 424.3B, 310.16, 240.4. ETC
 PLEASE KNOW, DEPENDING ON VOLTAGE OF SERVICE THE OCP
 DEVICES AS SHOWN MAY INDEED CHANGE.
  
 3) NOTE: PLEASE SHOW CALCULATIONS FOR TRACK LIGHTING
 PER 220.12B
  
 4) NOTE: PLEASE SEE SERVICE SHOWS 4-METERS , HOWEVER
 THIS IS BEING SHOWN AS ONE NEW TENANT BUILD OUT. PLEASE
 KNOW, IF THIS IS GOING TO BE FOUR SEPARATE TENANT
 SPACES, THEN PLEASE ADJUST.
 PLEASE SEE ONLY ONE TENANT SPACE IS BEING SHOWN W/OUT
 ANY FIRE/TENANT SEPARATION WALLS BEING SHOWN??
 PLEASE ALSO SEE A FORTH BEING SHOWN WITHOUT GOING TO
 ANYTHING?
 PLEASE KNOW THE SERVICE RISER AT THIS TIME IS UNCLEAR.
  
 230.2,
 FBC 106.1.2
  
 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS. PLEASE
 INDICATE ALL CONTINUOUS LOADS AT 125%.
 215.3, 230.42
 220.3,220.10,220.13,220.11 ETC.
  
 6) NOTE: PLEASE CLARIFY SIZE OF EXISTING MCB AND SEC'S
 FOR SERVICE.
 230.70, 240.4, 310.16
  
 7) NOTE; PLEASE SEE THE FOLLOWING CODES AT A MINIMUM
 SHALL BE STATED ON PLANS.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101
  
 8) NOTE: PLEASE SEE THE OVER RIDE DEVICES REQUIRED
 LOCATED AT THE POINT OF ENTRANCE INTO ANY ONE SPACE
 SHALL BE LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING
 CONTROLLED.
 PLEASE INDICATE THE MAX TIME ALLOWED ON OVER -RIDES,
 DEPENDING ON TYPE OF OR DEVICE BEING USED.
 IF IT THE INTENT TO COMPLY W/ FBC CHAPTER 13, PLEASE
 SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 30MINS MAX OCCUPANT TYPE/ 4HRS MAX ON TIMER TYPE
  
  
 ** PLEASE KNOW, AS THE A/C UNITS ARE BEIGN SHOWN AS 208
 AND SERVICE AT 240V, EITHER THE "M" SHEETS WILL BE
 REVISEDFOR THIS OR ELECTRICAL PLANS WILL BE. IF
 SERVICE IS INDEED 240V, PLEASE VOID AND REPLACE "M"
 SHEETS WITH NEW REVISED SHEETS INDICATING THE CORRECTED
 VOLTAGES.
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  
  