| 2006-10-12 19:54:52 | *** UNSAT *** |
| | |
| | 1) NOTE:PLEASE CORRELATE VOLTAGE FOR A/C SYSTEMS,. |
| | PLEASE SEE MECH PLANS INDICATE 208V AND ELECTRICAL |
| | PLANS INDICATE 240 V. |
| | |
| | 2) NOTE: PLEASE SEECONDUCTOR SIZES FOR AHU #2, PLEASE |
| | SEE , 424.3B, 310.16, 240.4. ETC |
| | PLEASE KNOW, DEPENDING ON VOLTAGE OF SERVICE THE OCP |
| | DEVICES AS SHOWN MAY INDEED CHANGE. |
| | |
| | 3) NOTE: PLEASE SHOW CALCULATIONS FOR TRACK LIGHTING |
| | PER 220.12B |
| | |
| | 4) NOTE: PLEASE SEE SERVICE SHOWS 4-METERS , HOWEVER |
| | THIS IS BEING SHOWN AS ONE NEW TENANT BUILD OUT. PLEASE |
| | KNOW, IF THIS IS GOING TO BE FOUR SEPARATE TENANT |
| | SPACES, THEN PLEASE ADJUST. |
| | PLEASE SEE ONLY ONE TENANT SPACE IS BEING SHOWN W/OUT |
| | ANY FIRE/TENANT SEPARATION WALLS BEING SHOWN?? |
| | PLEASE ALSO SEE A FORTH BEING SHOWN WITHOUT GOING TO |
| | ANYTHING? |
| | PLEASE KNOW THE SERVICE RISER AT THIS TIME IS UNCLEAR. |
| | |
| | 230.2, |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT LOAD CALCULATIONS. PLEASE |
| | INDICATE ALL CONTINUOUS LOADS AT 125%. |
| | 215.3, 230.42 |
| | 220.3,220.10,220.13,220.11 ETC. |
| | |
| | 6) NOTE: PLEASE CLARIFY SIZE OF EXISTING MCB AND SEC'S |
| | FOR SERVICE. |
| | 230.70, 240.4, 310.16 |
| | |
| | 7) NOTE; PLEASE SEE THE FOLLOWING CODES AT A MINIMUM |
| | SHALL BE STATED ON PLANS. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101 |
| | |
| | 8) NOTE: PLEASE SEE THE OVER RIDE DEVICES REQUIRED |
| | LOCATED AT THE POINT OF ENTRANCE INTO ANY ONE SPACE |
| | SHALL BE LOCATED SO THE OCCUPANT CAN SEE LIGHTING BEING |
| | CONTROLLED. |
| | PLEASE INDICATE THE MAX TIME ALLOWED ON OVER -RIDES, |
| | DEPENDING ON TYPE OF OR DEVICE BEING USED. |
| | IF IT THE INTENT TO COMPLY W/ FBC CHAPTER 13, PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | 30MINS MAX OCCUPANT TYPE/ 4HRS MAX ON TIMER TYPE |
| | |
| | |
| | ** PLEASE KNOW, AS THE A/C UNITS ARE BEIGN SHOWN AS 208 |
| | AND SERVICE AT 240V, EITHER THE "M" SHEETS WILL BE |
| | REVISEDFOR THIS OR ELECTRICAL PLANS WILL BE. IF |
| | SERVICE IS INDEED 240V, PLEASE VOID AND REPLACE "M" |
| | SHEETS WITH NEW REVISED SHEETS INDICATING THE CORRECTED |
| | VOLTAGES. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |