| Plan Review Notes For Permit 06100060 |
| Permit Number |
06100060 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-03 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- ROOF OVER INSTALLATIONS REQUIRE | | | PRE-INSPECTION. APPLICATION SENT TO KEN | | | CONRAD FOR PRE-INSPECTION. | | | | | | 2- CLEARLY IDENTIFY WHICH SPECIFIC | | | APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH | | | GENERAL LIMITATION #7 OR #9. IF SELECTED | | | SYSTEM IS LIMITED BY GENERAL LIMITATION | | | #7, THENCALCULATIONS SHALL BE DONE BY | | | ANY PROFESSIONAL LISTED IN SUCH | | | LIMITATION. SEE PAGE 25 OF 25 OF NOA | | | SUBMITTED. | | | | | | 3- SPECIFY ROOF AREA AND BUILDING MEAN | | | ROOF HEIGHT AS REQUIRED BY CITY POLICY | | | FOR ROOFING PERMITS. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|