| 2006-10-31 08:21:01 | |
| | |
| | REVISION DENIED |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} PLANS SUBMITTED FOR REVIEW MUST BE OF SUFFICIENT |
| | CLARITY FOR RECORD RETENTION AND REVIEW, PENCIL |
| | CLOUDING AND CROSSING OUT ITEMS DOES NOT MEET THE |
| | STANDARDS FOR CLARITY PER 106.3.1 FBC AS AMENDED. DO |
| | NOT COPY REVIEWED PLANS FOR REVIEW. |
| | |
| | 2} SMOKE DETECTORS MUST BE INSTALLED TO COMPLY WITH |
| | R313.1 RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 3} SOME CIRCUIT NUMBERS AREDESIGNATED AT THE DEVICES |
| | AND SOME ARE NOT, PLEASE CORRELATE. IF THE PANEL |
| | SCHEDULES ON THE DRAWING ARE NOT TO BE USED, REMOVE |
| | THEM FROM THE DRAWING. |
| | |
| | 4} LABEL THE ROOMS ON THE PLAN AS TO USE. |
| | |
| | 5} THE DELETED RECEPTACLE IN WHAT APPEARS TO BE BEDROOM |
| | #2, BETWEEN THE CLOSET AND ENTRY , MUST BE INSTALLED |
| | PER 210.52(A)(2), NEC. |
| | |
| | 6} THE BATH CIRCUIT REQUIRED TO HAVE A 20 AMP |
| | RECEPTACLE PER 210.11(C) (3), .INDICATE THE CIRCUIT ON |
| | THE PANEL SCHEDULE |
| | |
| | 7} CHECK THE LOAD CALCULATION FOR ACCURACY .ADD THE |
| | HEATING AND A/C AS REQUIRED BY 220.30 OR 220.31. VERIFY |
| | THE POOL PUMP, SPRINKLER PUMP AND WATER PUMP. |
| | |
| | 8} THERE IS A RANGE SHOWN ON THE PANEL SCHEDULE, AND ON |
| | THE CALCULATION A COOKTOP AND OVEN, PLEASE CORRELATE. |
| | |
| | 9} SHOW THE SMALL APPLIANCE CIRCUITS LOCATION ON THE |
| | PANEL SCHEDULE. CURRENTLY THEY ARE LISTED ON THE |
| | DW/COMPACTER CIRCUITS. |
| | |
| | 10} THE REFRIGERATOR IS LISTED ON THE GENERAL LIGHTING |
| | CIRCUIT IN VIOLATION OF 210.52(B)(1) |
| | |
| | 11} THE PLAN INDICATES THE PANEL WAS RELOCATED. PLEASE |
| | SHOW PREVIOUS LOCATIION AND ROUTING OF CONDUIT(S) TO |
| | NEW LOCATION. |
| | |
| | 12} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN |
| | MUST PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2, |
| | THIS INCLUDES THE ATTACHED PAGES. |
| | |
| | IF THERE ARE ANY QUESTIONS CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | FAX/:561/805-6676 |
| | |
| | |
| | |