| Plan Review Notes For Permit 06100038 |
| Permit Number |
06100038 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-12 08:28:48 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE VALUE ON THE APPLICATION MUST | | | INCLUDE THE TOTAL COST OF LABOR AND | | | MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF | | | NATIONAL CONSTRUCTION COST ANALYSIS | | | SERVICES PER 108.3 FBC AS | | | AMENDED. INCREASE THE VALUE AT THE | | | COUNTER AND RESUBMIT. | | | | | | 2} PLEASE SUBMIT FLOOR PLANS INDICATING THE SCOPE OF | | | WORK, ONLY LOAD CALCULATIONS AND PANEL SCHEDULES WERE | | | SUBMITTED. | | | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.2.FBC AS | | | AMENDED. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | FAX/:561/805-6676 |
|