| 2006-10-13 07:19:21 | **** UNSAT *** |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC CHAPTER 13 13-415.1.ABC.1.1, |
| | .1.2 AND .1.3. |
| | PLEASE ALSO SEE 13-415.2.ABC.1. PLEASE SEE THIS SPACE |
| | WAS A "SHELL" SPACE AND IS NOW BEING BUILT OUT UNDER |
| | THE 2004 FBC. PLEASE ADJUST AS NEEDED. |
| | |
| | 2) NOTE: PLEASE VERIFY THE EXISTING EXIT LT BEING SHOWN |
| | FROM SPACE LEADING TO STAIR TOWER. PLEASE KNOW, THE |
| | CIRCUITING SHALL MEET 700.12E. PLEASE SHOW. |
| | |
| | 3) NOTE: PLEASE CLARIFY THE PANEL SCHEDULE MENTIONS A |
| | "RECEPT" FOR THE INSTA-HOT. PLEASE SEE 430.30, 430.31 |
| | ETC AS LOAD OF THIS SIZE WHEN UNIT IS REQUIRED TO |
| | CONTAIN A DISCONNECT , A PLUG MAY NOT BE USED. PLEASE |
| | ALSO VERIFY IF THE DISCONNECTING MEANS CONTAINS OCP, IF |
| | SO ,PLEASE SEE 110.26. |
| | |
| | 4) NOTE: PLEASE SEE PLANS ARE CALLING THE ROOM WHERE |
| | THE ELECTRICAL PANELS ARE LOCATED AS "IT" ROOM?? PLEASE |
| | VERIFY AS IF THIS IS INDEED GOING TO BE AN "IT" ROOM, |
| | PLEASE SEE NFPA-75, AND NFPA-70 645 FOR REQUIREMENTS. |
| | PLEASE SEE CHAPTER TWO OF 75 AS TO DEFINITION AND |
| | CHARACTERISTICS OF SUCH A ROOM. |
| | |
| | 5) NOTE: PLEASE SEE VALUE FOR COMPLETE SCOPE OF WORK |
| | SHALL BE BASED ON ALL LABOUR AND MATERIALS EVEN IF |
| | OWNER SUPPLIED. |
| | FBC 108.3 |
| | PLEASE SEE $25K IS WAY LOW. PLEASE KNOW, USING TABLES |
| | BASED ON THE FBCONE WILL BE ASSESSED. FEES WILL BE |
| | OWED. |
| | |
| | 6) NOTE: PLEASE KNOW, THIS INTERIOR BUILD OUT WILL |
| | REQUIRE A NEW NOTICE OF COMMENCEMENT AS THE ONE UDNER |
| | THE BUILDING AHS EXPIRED AND IS NOT PARTOF THIS SCOPE |
| | OF WORK. FS 713.13 |
| | |
| | 7) NOTE: PLEASE INDICATE AND SHOW LOAD SUMMARY AND |
| | CALCULATIONS INCLUDING ALL CONTINUOUS LOADS AT 125%. |
| | 220.3,220.10,220.11,220.13, ETC 215.3, 230.42 |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |