| 2006-10-17 18:48:07 | *** UNSAT **** |
| | |
| | 1) NOTE: PLEASE SHOW AND VERIFY THE GROUNDING ELECTRODE |
| | ATTACHMENT LOCATION FOR THE SEPARATELY DERIVED |
| | TRANSFORMER.. 250.66, 250.30, 250.22 |
| | |
| | 2) NOTE: PLEASE VEIRFY THE EXSITING CONDCUCTORS FOR THE |
| | SECONDARY SIDE OF THE EXISTING TRANSFORMER AS IT SEEMS |
| | TO BE SHOWN FURTHER THAN CODE PERMITS. PLEASE ALSO |
| | VERIFY OF THE EXISTING 120/208 VA PANEL CONTAINS A MCB. |
| | 408.16, 240.21 |
| | |
| | 3) NOTE: PLEASE PROVIDE LOAD ON THE EXISTING SERVICE IN |
| | WHICH WE ARE NOW INCREASING LOAD ON. PLEASE SEE |
| | EXISTING WAS 100A'S AND ONLY SHOWS THE NEW LOAD ON THE |
| | NEW 200A PANEL?? |
| | 220, 215.3, 230.42 |
| | |
| | 4) NOTE: PLEASE VERIFY THE OCP DEVICES AND CONDUCTOR |
| | SIZES WHICH WILL BE PLACED INOT THE NEW 200A PANEL. |
| | 240.4, 310.16, 408.4. PLEASE LIST ON SCHEDULE. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |