| 2007-03-07 16:11:05 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | CITY WEST PALM BEACH MUNICIPAL CODE |
| | |
| | 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE |
| | 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT |
| | LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH |
| | THEY ARE INSTALLED. |
| | ****RESPONSE NOTED, BUT AN RPZV BACKFLOW IS REQUIRED ON |
| | THE WATER SUPPLY TO THE BUILDING. SHEET C-3 NOW |
| | INDICATES THE WATER SUPPLY CONNECTING TO TWO SOURCES. A |
| | 2" LINE AND A 1-1/2" LINE. PLEASE CLARIFY. SECTION |
| | 608.13.2. ALSO SEE SHT P-3 AT THE INCOMING MINIMUM 2" |
| | WATER SUPPLY INDICATES A BACKFLOW REQUIRED. |
| | |
| | 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE |
| | REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL |
| | COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561) |
| | 822-2279, OR E-MAIL [email protected]. UTILITY ORD. |
| | 3434. |
| | ****RESPONSE NOTED, BUT THE REQUIREMENT FOR A SAND/OIL |
| | INTERCEPTOR SHALL BE DETERMINED BY ENVIRONMENTAL |
| | COMPLIANCE. ARTICLE III SECTION 90-124(7) OF THE |
| | MUNICIPAL CODE. LOOKING THROUGH APPENDIX "I", THERE ARE |
| | 14 PAGES OF INFORMATION. IF THERE IS INFORMATION ON A |
| | SAND/OIL INTERCEPTOR IN THESE PAGES, PLEASE INDICATE |
| | WHICH PART AND SUBPART PRETAINS TO THIS INFORMATION. |
| | WILL THIS INFORMATION INDCATE IF THE OVERFLOWS WILL |
| | HAVE THE OIL INTERCEPTED? |
| | |
| | |