| 2007-02-27 07:53:32 | *** UNSAT 2ND REVIEW*** |
| | |
| | |
| | |
| | 1) NOTE:PLEASE KNOW, PLANS HAVE STILL ONLY BEEN |
| | SUBMITTED FOR "PLAN REVIEW" AND HAVE NOT BEEN SUBMITTED |
| | FOR PERMIT AT THIS TIME. |
| | AS PERMIT APPLICATION WAS NOT MADE BEFORE DECEMBER 8TH, |
| | 2006 ALL PLANS, DESIGNS,AND CODES REFLECTED ON PLANS |
| | WILL BE UNDER THE NEW CODES AS ADOPTED BY THE STATE OF |
| | FLORIDA. |
| | PLEASE SEE THAT THE PLANS ARE SHOWING INCORRECT CODES |
| | AT THIS TIME. |
| | 2004 FBC W/2006 REVISIONS. |
| | 2005 NFPA-70 |
| | PLEASE KNOW THAT THE "LATEST EDITION? MAY NOT BE STATED |
| | ON PLANS. |
| | THIS IS REQUIRED FOR ALL SHEETS AND TRADES WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER TRADES OR REVIEWS. |
| | IF PLANS CONTAINED ALL THE CORRECT CODES AND WERE CODE |
| | COMPLIANT, THE REVIEW COULD NOT BE ?PASSED? AS PERMIT |
| | APPLICATION HAS NOT YET BEEN MADE AND REVIEW OF SCOPE, |
| | PERMIT APPLICATION AND VALUATION OF PROJECT STILL NEEDS |
| | TO TAKE PLACE. |
| | |
| | 2) NOTE: PLEASE PROVIDE LOAD CALCULATIONS ON ALL |
| | SERVICE EQUIPMENT ON THE LINE SIDE OF THIS TRANSFORMER |
| | IF NOT A FPL UNIT. |
| | 220, FBC 106.1.2 |
| | THIS WAS REQUESTED ON THE PREVIOUS REVIEW HOWEVER LOAD |
| | SUMMARY OR CALCULATIONS FOR THE EXISTING MAIN DIST SWGR |
| | HAS NOT BEEN PROVIDED. |
| | |
| | 3) NOTE: PLEASE INDICATE ALL BRANCH CIRCUIT CONDUCTORS |
| | ON PANEL SCHEDULE. PLEASE SEE 310.16 FOR SIZING. |
| | 240.4, 310.16, |
| | FBC 106.5.3.1.2 |
| | *SOME CONDUCTOR SIZES ARE SHOWN ON PLANS AND NOTE WAS |
| | VIEWED FOR OTHER CONDUIT RUNS, HOWEVER NOT ALL AND |
| | PLEASE PLACE ON PANEL SCHEDULE. |
| | |
| | . |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-02-26 07:03:19 | 2007-02-25 07:03:19 |
| | IN PROGRESS |
| 2007-02-25 14:55:45 | 2007-02-25 14:55:45 |
| | REVIEW WILL CONTINUE, PLANS WILL FOLLOW INTO "F" STATUS |
| | ONCE REVIEW IS COMPLETED. |