| 2007-03-02 10:37:46 | DENIED BY BUILDING |
| | PLAN REVIEW |
| | 6255 N. JOG RD. |
| | SWA TRUCK WASH |
| | TYPE II-B / FULLY SPRINKLERED |
| | |
| | 1)ITEMS 1-4 OF FIRST REVIEW WILL APPLY WHEN |
| | SUBMITTING FOR PERMIT. |
| | |
| | 2) SIGNED AND SEALED COPIES OF THE GEOTECHNICAL REPORT |
| | FROM TIERRA ARE REQUIRED. |
| | |
| | 3) IN REGARDS TO THE RESPONSE TO ITEM # 8 OF THE FIRST |
| | REVIEW. THE FIRE SPRINKLER INCREASE ALLOWED BY FBC |
| | 506.3 REQUIRES THE BUILDING TO BE EQUIPPED THROUGHOUT |
| | WITH AN APPROVED SPRINKLERED IN ACCORDANCE WITH FBC |
| | 903.3.1.1. THIS MEANS THAT BOTH OF THE BUILDINGS ARE |
| | REQUIRED TO BE FULLY SPRINKLERED. THE ALLOWABLE AREA IN |
| | TABLE 503 IS PER FLOOR. THEREFORE, THE SQUARE FOOT AREA |
| | OF THE DOES NOT NEED TO BE INCLUDED IN THE CALCULATIONS |
| | FOR THE FIRST FLOOR. THIS INFORMATION SHOULD BE ON THE |
| | PLANS. |
| | |
| | 4) IN REGARDS TO ITEM #9 REQUESTING ENERGY |
| | CALCULATIONS. SUBMIT A SIGNED AND SEALED LETTER |
| | SPECIFYING WHICH ONE OF THE EXEMPTIONS IN FBC |
| | 13-101.5.7 APPLIES AND WHY. |
| | |
| | 5) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. SEE #12 ON FIRST REVIEW. THE PRODUCT APPROVALS |
| | SUBMITTED ARE NOT ACCEPTABLE. THE INSTALLATION |
| | INSTRUCTIONS AND DESIGN PRESSURES ARE REQUIRED. THESE |
| | ARE TYPICALLY INCLUDED IN THE EVALUATION REPORT OR NOA |
| | THAT WAS SUBMITTED TO THE STATE. |
| | |
| | 6)WPB ADMIN CODE 106.3* PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) THE PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY A |
| | FLORIDA REGISTERED ARCHITECT OR ENGINEER. FS 471 AND |
| | 481. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |