| Plan Review Notes For Permit 06100017 |
| Permit Number |
06100017 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-12-06 14:22:35 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | CITY WEST PALM BEACH MUNICIPAL CODE | | | | | | 1. SHT C-3 INDICATES A 1" RPZV BACKFLOW. PER TABLE | | | 60.1(D),ALL SECONDARY BACKFLOW ASSEMBLIES SHALL BE AT | | | LEAST THE SAME SIZE AT THE WATER SERVICE LINE IN WHICH | | | THEY ARE INSTALLED. | | | | | | 2. SHTS P-1 & P-2 A SAND/OIL INTERCEPTOR MAY BE | | | REQUIRED. PLEASE CONTACT LYNN MASSON, ENVIRONMENTAL | | | COMPLIANCE MANAGER AT (561) 822-2271, OR FAX (561) | | | 822-2279, OR E-MAIL [email protected]. UTILITY ORD. | | | 3434. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|