| Plan Review Notes For Permit 06100017 |
| Permit Number |
06100017 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-30 18:23:25 | ------------DENIED-------------- | | | 1. PLEASE PROVIDE DETAIL FOR THE WALL SLEEVE/ LOUVER/ | | | FIRE DAMPER ATTACHMENTS SHOWING COMPLIANCE WITH FIRE | | | DAMPER MANUFACTURER'S INSTALLATION INSTRUCTIONS PER | | | FBC,M 607.2 | | | | | | 2. AUXILIARY DRAIN PROTECTION IS REQUIRED ON AHU PER | | | FBC,M 307.2.3 | | | | | | 3. CONDENSATE DISPOSAL TO BE IN COMPLIANCE WITH FBC,M | | | 307.2.1 AND FBC 1503.6 | | | | | | 4. FAN SHUT-DOWN BY SMOKE DETECTOR IS REQUIRED ON AHU | | | PER FBC,M SECTION 606 | | | | | | 5. PLEASE PROVIDE DETAIL FOR C.U. ATTACHEMNT TO SLAB | | | SHOWING COMPLIANCE WITH FBC,M 301.13 | | | | | | REVIEWED BY: | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|