| 2006-12-13 16:03:35 | *****DENIED***** |
| | |
| | |
| | |
| | |
| | 1.THE ADDRESS OF THE TRUCK WASH FACILITY SHALL BE IN |
| | THE TITLE BLOCK OF EACH SUBMITTED PLAN. |
| | |
| | 2.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE ELEVATION (SHEET A-2).AS PER WEST PALM |
| | BEACH CODE, THE NUMERICAL ADDRESS SHALL BE NO LESS THAN |
| | 6" IN HEIGHT AND 1"IN WIDTH. |
| | |
| | 3.NFPA 101 (2003 EDITION) AND THE FLORIDA FIRE |
| | PREVENTION CODE (2004 EDITION) SHALL BE REFERENCED. |
| | |
| | 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 5.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| | PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 6.ACCESS ROADS SHALL BE CAPABLE OF SUPPORTING AND |
| | MAINTAINING 32 TONS OF FIRE EQUIPMENT. |
| | |
| | 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE SPRINKLER SYSTEM.NFPA 13 (2002 EDITION) SHALL BE |
| | REFERENCED. |
| | |
| | 8.WHEN IT IS NECESSARY TO SHUT DOWN A FIRE PROTECTION |
| | SYSTEM (IF NEEDED TO RELOCATE THE FIRE DEPT. CONN. AS |
| | STATED ON SHEET FP-1.0) , THE FIRE DEPARTMENT SHALL BE |
| | NOTIFIED WHEN THE SYSTEM IS SHUT DOWN AND WHEN IT IS |
| | RETURNED TO SERVICE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED. |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |