2006-10-30 16:54:02DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT T-1 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. PLEASE CORRELATE THE INDEX WITH
 SHEETS SUBMITTED. SECTION 106.1.1.
  
 2. SUBMIT INFORMATION ON REVELANT DESIGN CODE. SECTION
 106.1.2.
  
 3. INDICATE OCCUPANCY. SECTION 106.3.5.1.1(2).
  
 4. SUBMIT A DETAIL FOR THE BREAK ROOM, (104), SINK.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 5. A DRINKING FOUNTAIN IS REQUIRED PER TABLE 403.1.
 SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.15
 AND ALL SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A)
 PROVISIONS FOR THOSE WHO HAVE TROUBLE BENDING OR
 STOOPING.
  
 6. SHT P-1.01 PLUMBING FIXTURE P-1 ELKAY LR17720 NOT
 APPROVED FOR AN ACCESSIBLE SINK. MAXIMUM SINK DEPTH IS
 6-1/2". MODEL SHOWN INDICATES THE SINK DEPTH AS 7-1/2".
 SECTION 11-4.24.4. (SEE ATTACHED SHEET).
  
 7. SHT P-1.O1 DOMESTIC WATER RISER ISOMETRIC. A WATER
 HAMER ARRESTOR IS REQUIRED FOR THE DISHWASHER ON EH
 WATER LINE. SECTION 604.9.
  
 REVIEW BY KEN STEVENS