| Plan Review Notes For Permit 06091103 |
| Permit Number |
06091103 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-23 19:02:37 | ----------------DENIED--------------- | | | | | | 1. MECHANICAL PLANS WERE NOT SIGNED AND SEALED BY THE | | | ENGINEER. | | | | | | 2. ROOMS 102 & 109 ARE NOT IN COMPLIANCE WITH FBC,M | | | 601.4 WHICH REQUIRES BALANCED RETURN FROM ALL HABITABLE | | | ROOMS. PLEASE SHOW COMPLIANCE WITH EXCEPTION #2 UNDER | | | THIS SECTION OR DEMONSTRATE HOW BALANCED RETURN IS TO | | | BE ACHIEVED IN THESE AREAS. | | | | | | 3. ROOF PENETRATION DETAIL SHOWS REFRIGERANT PIPING | | | PENETRATING A CONCRETE SLAB TO THE ROOF. PIPING | | | PENETRATING CONCRETE FLOORS OR CEILINGS SHALL BE | | | PROVIDED WITH A SLEEVE OR THIMBLE PER FBC,M 1107.2.1. | | | PLEASE PROVIDE DETAIL SHOWING COMPLIANCE. | | | | | | RONALD J REGUEIRO | | | 561.805.6734 | | | [email protected] |
|